Comm and Fault Indicators

The PanelView 300 Micro has a Comm (communication) and Fault (error) status
indicator. These indicators are visible from Configuration Mode when selecting
the Communication screen. Use the Comm and Fault indicators to isolate
operating problems.
CONFIGURATION MODE
Language
Communication
Preset Operations
F1 RUN MODE
F2 RESET VIDEO
Indicator
State
Comm
ON (steady state solid fill)
OFF (no fill)
Blinking (flashing)
Fault
OFF (no fill pattern)
ON (steady state solid fill)
Blinking (flashing)
C
F
Indicates
Normal Operating (no communications fault)
Fault detected. Verify:
• controller is in run mode.
• communication settings for terminal and
controller.
• terminal and controller node addresses.
• terminal to controller connections.
No communications established. For DF1 terminals,
the Comm indicator flashes until an application is
loaded.
Normal operating state
Fault detected. Reset or cycle power to the terminal.
If the fault remains the terminal requires servicing.
Hardware is functioning but no application is loaded
in the terminal or the current application is
corrupted. Reload the application file into the
terminal.