Herunterladen Inhalt Inhalt Diese Seite drucken

Installation - Siemens OZW772 series Installationsanleitung

Web-server
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 7
en
English

Installation

• Make sure service has space to install connecting cables and has
easy access the unit.
Mounting and wiring
2
3
4a
/
See figures
Preparation
2
1.
Take off cover
2.
Insert cable tie for KNX cable
4a
Standard mounting on standard rail TH 35-7.5
1.
Mount standard rails
2.
Attach web server to standard rails from above
3.
Push down the web server until it locks
4b
Screw on mounting on a level wall
Drill two holes for the screws ∅ max. 3.5 mm
1.
2.
Tighten web server and make sure it is flat (warped housings are
not permitted)
Wiring and final mounting
1.
Switch off KNX devices
2.
Connect KNX cable, terminal 2: CE+, terminal 3: CE−
3.
Tighten cable tie and cut off the remainder
4.
Break out the notch from the cover
8
5.
Replace the cover
Display and operating elements
12
See figure
page 4
LED displays
1 On
(green/red)
Dark
No power
Steady red
Web server starting (operating system)
Flashing red
Web server starting (application)
Steady green
Web server operational
2 KNX
(green)
Dark
No bus power
Lit
KNX operational
Flashing
Communication on KNX
3 Reserve
Dark
No function
4 Fault
(red)
Displays faults from the web server or the connected KNX devices.
Dark
No fault
Lit
Acknowledged fault
Flashing
Unacknowledged fault
5 Addressing mode (red)
Dark
KNX addressing mode off
Lit
KNX addressing mode on
Operating buttons
The following applies when pressing the buttons
Short:
< 2 seconds
Long:
> 6 seconds
6 Remote
Short
Acknowledges fault message
Long
Sends system report to the configured receiver;
see as well "Button combination".
7 Addressing mode
Short
One-time press sets the web server to the KNX ad-
dressing mode. Pressing the button again switching off
the KNX addressing mode.
Long
See "Button combination"
Siemens Building Technologies
4b 5 6 7 8
page 2, 3
3
5
6
7
Button combination
and
Short
No function
Long
Reestablishes default state
Note: This resets all configuration data and settings.
The device list, plant diagrams and all unsent mes-
sages are deleted. History data is not deleted.
Commissioning
9 10 11 12 13 14
See figures
Prerequisites
• The web server is mounted and wired
• The connected KNX devices are commissioned
• The KNX devices have a valid KNX address [1...253] and are
operational
• Bus power supply to the KNX bus is turned on
• The web server / a connected KNX device is the clock time master
on KNX
Notes
• IP address USB:
192.168.250.1
IP address Ethernet:
192.168.251.1
• Commissioning with a PC/laptop and a web browser via the USB
interface. The RNDIS driver must be installed to connect via USB.
• The RNDIS driver is automatically installed when connected via
USB when the PC/laptop is connected to the Internet.
• The RNDIS driver is supplied on the web server at
http://<IP address>/drivers/
• Additional information on commissioning is included in the detailed
Commissioning instructions C5701. It is stored on the web server at
http://< IP address>/doc/
• To navigate, always start with primary navigation, then use the
secondary navigation to select the desired menu item (see
page 5).
• Return navigation: Click the "Upward" symbol
path (bread crumb) or primary navigation.
Preparations
1.
Turn on the power to the web server. The web server is opera-
tional, when the green ON LED is lit.
2.
Plug in the supplied USB cable on the web server (connection B,
12
see
page 4) and PC. The PC recognizes the web server as
a USB device.
Log onto web server
3.
Start web browser. In the address line, enter the USB IP address
(192.168.250.1).
4.
Login:
• User name: Administrator
• Password: Password
• Click [Login] to finish
Administer user accounts
5.
Edit administrator data:
• From the primary navigation (above), select "User accounts"
• Click red pencil symbol
• In the mask "Change user" enter:
• Password
• Repeat password
• Description (optional)
• E-mail address (optional)
• Language: English
• Click [OK] to finish
74 319 0664 0 b
G5701xx
page 3, 4, 5
9
10
11
(cannot be changed)
(default value)
14
or navigate via
14.01.2010
en 7/8

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ozw772.01Ozw772.04Ozw772.16Ozw772.64

Inhaltsverzeichnis