If all conditions are met, the product is ready for operation.
1.
Power on using the site-side mains fuse.
The green power indicator and red alarm light up.
Ä
WMS 2-1 manually release using the "Release" button or via the external
2.
releasing device.
During normal operation the red alarm lamp is unlit and the burner starts up.
Ä
4.
Perform a functional check; see Chapter 6.5, Page 18.
6.5

Functional check

A functional check is performed manually by reducing the water level below the trigger
threshold, or by pulling the inner, movable electrode upwards.
This functional check must be carried out at regular intervals.
Perform the functional check 1 x per year and after any maintenance or repairs.
f
At the sensor
1.
For the functional check, pull up the electrode rod to its upper limit for at least 1
second.
The electrode rod is no longer in the boiler water, which simulates a lack of
Ä
water.
The red alarm lamp on the control unit is lit, and the burner automatically shuts off.
Ä
2.
Press the release button on the control unit to return to normal operating state.
The red alarm lamp is unlit and the burner is operational.
Ä
At the signaling unit
1.
Press the test button for at least 1 second.
The connection to the sensor is interrupted and the red alarm lamp is lit.
Ä
The burner shuts off automatically.
Ä
2.
Press the release button on the control unit to return to normal operating state.
The red alarm lamp is unlit and the burner is operational.
Ä
16
ENG: Installation and operating instructions
Translation of the original operating instructions