Electrical Connection - flamco WMS 2-1 Montage- Und Betriebsanleitung, Originalbetriebsanleitung

Wassermangelsicherung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2.
Wire the electrical connection as per Chapter 6.3, Page 15.
3.
Close signaling unit.
6.3

Electrical connection

Mains voltage is interrupted and secured against switching back on.
R
Call in a qualified electrician to perform the electrical installation work.
f
f
Observe VDE requirements, accident prevention regulations and operating instructions
for the WMS, boilers and burner.
The power supply cable for the boiler room must be equipped with a main
R
switch outside the boiler room that simultaneously isolates all ungrounded
conductors with at least a 3 mm contact gap.
Power supply
Den Netzanschluss mit einer festverlegten Leitung z. B. NYM-O 2 x 1,5 mm² herstellen.
1.
Route the power supply cable through the right-hand compression coupling in
the signaling unit.
2.
Route the phase conductor to terminal L1 and the neutral conductor to terminal
N.
3.
The supply cable to the signaling unit must be separately fused (max. 10 A).
13