1.7 Rate
Sets the reaction speed of the device to measurement changes in the target range.
Options
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy, faster settings allow for more level fluctuation.
1.8 Apply Changes (APPLY?)
In order to save the Quick Start settings it is necessary to enable Apply Changes.
YES, NO
Options
Select YES. SITRANS LR460 is now ready to operate and returns to RUN mode.
Communication via HART or PROFIBUS PA
Notes:
• The Quick Start settings are not independent parameters. The settings are inter-
related, and changes only apply when you click Transfer at the end of step 4.
• Do not use the Quick Start Wizard to modify individual parameters. See the full
manual for detailed instructions.
Quick Start Wizard via SIMATIC PDM
The graphical Quick Start Wizard groups together all the settings you need to make for a
simple application into 4 steps.
To use HART or PROFIBUS PA, you will need a PC configuration tool: we recommend
SIMATIC PDM.
Please consult the operating instructions or online help for details on using SIMATIC PDM.
(Application Guides for setting up SMPI HART and PROFIBUS PA instruments with SIMATIC
PDM are available on our website: www.siemens.com/processautomation.)
Device Description (DD)
You will need the most up-to-date DD for SIMATIC PDM version 6.0 with SP2 HF1 (or higher).
You can locate the DD in Device Catalog, under Sensors/Level/Echo/Siemens Milltronics/
SITRANS LR460. If you do not see SITRANS LR460 under Siemens Milltronics, you can
download the DD from the product page of our website at: https://pia.khe.siemens.com/
index.asp?Nr=14655, under Downloads.
Save the files to your computer, and extract the zipped file to an easily accessed location.
Launch SIMATIC PDM – Manager Device Catalog, browse to the unzipped DD file and select it.
Configuring a new device
1.
Set Address (default for PROFIBUS PA is 126; for HART is 0).
Point the handheld programmer at the display then press Mode
PROGRAM mode, menu item 1.
7ML19985QW82
SLOW
0. 1 m/minute
MED
1.0 m/minute
FAST
10.0 m/minute
SITRANS LR460 – QUICK START MANUAL
to activate
Page EN-13