Herunterladen Inhalt Inhalt Diese Seite drucken

Charging Additional Refrigerant - Mitsubishi Electric CITY MULTI PURY-P-YNW-A-BS Serie Installationshandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 63

9-9-2. Charging additional refrigerant

Charge the calculated amount of refrigerant in the liquid state to the unit through the service port after the completion
of piping work. Upon completion of all work, securely tighten all service port caps and shaft caps to prevent refrigerant
leakage.
<Notice>
・Do not vent the refrigerant into the atmosphere.
・Refer to the table below for the appropriate tightening torque.
Pipe size [mm (in)]
Shaft cap (N·m)
ø22.2 (ø7/8)
ø28.58 (ø1-1/8)
・If the refrigerant tank does not have a siphon pipe, charge the liquid refrigerant with the tank upside-down as shown
in the figure below.
・After evacuation and refrigerant charging, ensure that the service valves are fully open. Do not operate the unit
with the service valves closed.
WT08432X01
Shaft (N·m)
Size of hexagonal wrench [mm (in)]
22
-
22
-
-
-
GB-40
Service port cap (N·m)
16
16
Siphon pipe

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

City multi pury-ep-ynw-a-bs serie

Inhaltsverzeichnis