Ip-zentrale

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
GB
Function
The IP central unit is the interface between the Ethernet LAN (Local
Area Network) and the instabus EIB. With an Ethernet connection, the
user has access from the local PC of his LAN or also via the Internet to
his instabus EIB system.
The Internet connection can be established via DSL, LAN (RJ45-port)
or also with a V90 modem / ISDN-adapter (RS232 port).
The IP central unit acts as a server and can be comfortably operated
as a central control, reporting and checking unit with the web browser
©
of a PCs (Microsoft
Internet Explorer from V 5.5 onwards) or other
suitable LAN devices as, for instance, a PDA.
Characteristics
User-controlled commissioning and configuration assistant, system
clock functions, central year timer switch with astro function and day
profiles, presence simulation, logic functions, event reporting function
via e-mail, integrated e-mail address book, central functions, light-
scenes, scenes for HVAC and alarm system applications, etc.
22
Function + Characteristics
Directory server + Modes of operation
Directory server
Data exchange with the IP central unit via the Internet requires the use
of a directory server. A directory server is a server which can be reached
via Internet and which is the interface between a PC and the IP central
unit. When accessed from the web browser, a web page of the directory
server opening up a portal is first called up. The directory server checks
the connection or establishes the connection with the IP central unit.
When the connection has been established, access via the open portal
to the IP central unit is possible after verification of the access data.
Modes of operation
Depending on the existing system equipment, the IP central unit can
be operated in different modes.
- operation in an LAN
- operation in an LAN via a dedicated phone line to the Internet
- operation in an LAN with dial-in connection to the Internet and
triggering via modem (analog or ISDN)
- operation in an LAN with triggering or a-b port behind a telephone
system
- operation in a telephone system with dial-in to the Internet via
modem (analog or ISDN)
The Connection required in each case is shown in the pictures below.