7 PROTECTION SYSTEMS

The inverter is equipped with protection systems designed to preserve the pump, motor, power line and the
inverter itself. When one or more protections trip, the one with the highest priority is shown on display.
Depending on the type of error, the electric pump may shut down, but when normal conditions are restored,
the error state may clear automatically, immediately or after a set time interval following automatic reset.
In the case of a block due to water supply failure (BL), block due to pump motor current overload (OC), block
due to final output stage current overload (OF), block due to direct short circuit between the phases on the
output terminal (SC), the user can attempt to manually reset the error condition by pressing and releasing
buttons + and - simultaneously. If the error condition persists, the cause of the fault must be located and
eliminated.
Display message
PD
Irregular shutdown
FA
Problems with cooling system

Table 28: Alarms

Display message
BL
Block due to water failure
BP
Block due to pressure sensor reading error
LP
Block due to low power supply voltage
HP
Block due to high internal power supply voltage
OT
Block due to overheating of final power stages
OB
Block due to overheating of printed circuit
OC
Block due to current overload on electric pump motor
OF
Block due to current overload on final stages of output
SC
Block due to direct short circuit between the phases on the output terminal
EC
Block due to lack of rated current setting (RC)
Ei
Block due to "i" internal error
Vi
Block due to "I" internal voltage outside tolerance

Table 29: Block information

7.1 Description of blocks
7.1.1
"BL" Block due to water failure
In flow conditions below minimum value, with pressure lower than the set regulation value, a water failure
signal is emitted and the system shuts down the pump. The delay interval without pressure and flow can be
set in the parameter TB of the TECHNICAL ASSISTANCE menu.
If the user inadvertently enters a pressure setpoint higher than the pressure that the electric pump can
supply on closure, the system indicates "block due to water failure" (BL) even if this is not precisely the
problem. In this case, lower the regulation pressure to a reasonable value, which does not normally exceed
2/3 of the head of the electrical pump installed.
ENGLISH
Alarm in fault log
Description
Block conditions
Description
104