13 Configuration

Einstellen der Pufferzeit
Power-Fail (PF)-Timer
Shutdown-Timer
NORMAL
V
IN
V
OUT
44
DC2412-UPSD | DC2412-UPS-LDD | UPSIC-1205D | UPSIC-2403D
Concerns the backup time. The time during a power
failure after which a shutdown signal is sent to the PC
or host. If within this time the mains voltage returns
to the input, nothing will be done. This command
can either be forwarded to the PC or host via „UPS
Control Center" software (RS232 connection via D-SUB
required) or via Power Button Press (via PBR + / PBR -).
Concerns the time which is available for the system to
shut down safely. After expiry of the PF-Timer this time
is used to shut down the PC or host. When this time has
elapsed, the output is cut off for 8s. If the input voltage
returns during this time the output still remains cut off
to initiate a new restart of the system.
PF-TIMER
SHUTDOWN-TIMER
REBOOT= 8s