Operating Instructions
output does not change
High switching frequencies
are not transmitted
Self test
In order to check basic functions of the device, you may apply the following test steps.
Please disconnect the exchangeable terminals first. (see 6.3)
Connect the device to the power supply (via pac bus or directly via terminals 7
and 9)
Deactivate the line fault detection my means of the DIP switches at the front of
the device.
Establish an electrical connection between terminal 10 and 11 (in case of dual
channel devices additionally between terminal 14 and 15)
The LED "OUT" (yellow) lights up. It indicates that the output has switched. If you
disconnect the connection between the terminals the LED turns dark. The result
of this test indicates that input signals are processed.
Activate the line fault detection. The LED "LF" lights up no matter if the
connection between the terminal is established or not.
If the procedure described above does not obtain the desired result, please contact your
local R.STAHL sales and service representative. In order to quickly process your request,
please provide us with the following information:
 Type and serial number
 Purchase date
 Description of malfunction
 Application description (particularly the configuration of the input/output circuitry)
10

Accessories and spare parts

Use only original spare parts from R. STAHL Schaltgeräte GmbH.
22
Switching Repeater Type 9170
The electronic output is optimized for
the application along with active I/O
cards. In case of passive I/O cards
the potential for the generation of
High Level is missing.
The High Level can be generated if an resistor
is connected externally to the supply voltage
(e.g. +5V).