SIRIUS
MSS DP Interface Module
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
Taking the ambient conditions into consideration the devices must be
mounted into control cabinets with degree of protection IP32, IP43 and IP54.
Important note
The products described herein are designed to be components of a customized
machinery safety-oriented control system. A complete safety-oriented system
may include safety sensors, evaluators, signaling units and concepts for ensur-
ing safe switch-off. It is the responsibility of each manufacturer to ensure the
correct overall functionality of its systems and machines. Siemens AG, its
subsidiaries and affiliates (collectively "Siemens") are not in a position to
guarantee all of the characteristics of a given system or product not designed by
Siemens.
Siemens accepts no liability for any recommendation that may be implied or
stated herein. The warranty contained in the contract of sale by Siemens is the
sole warranty of Siemens. Any statements contained herein do not create new
warranties or modify existing ones.
Areas of Application
The DP interface represents an expansion device for MSS basic devices. It
allows communication of MSS basic devices with memory-programmable logic
controllers via PROFIBUS DP. The DP interface is not fail-safe, i.e. the
DP interface only transmits the information with the same reliability which can
also be achieved with other PROFIBUS components. Transfer is, therefore,
"unsafe".
Installation
Mounting
Figure Ia:
Screw mounting
Figure Ib:
Mounting onto standard mounting rail (1)
Demounting from standard mounting rail (2)
Dimension drawings (figure II)
3RK3511-1BA10
DP interface module with screw-type terminal
3RK3511-2BA10
DP interface module with spring-loaded terminal
Connection
.
Use a power supply unit that complies with IEC 60536
safety class III (SELV or PELV)!
Plugs and terminals (figure III)
PROFIBUS DP (9-pin D-Sub)
Pin assignment acc. to EN 50170
X1
Plug for connection to a PC
X2
Plug for connection to an MSS basic device plug X1
L+
24 V DC
M
Ground to 24 V DC
FE
Functional ground
Figure IV:
Connecting the spring-loaded terminals
Figure V:
Connection cross-sections and tightening torques
Figure VI: Connecting the ribbon cables
Figure VII: Replacing the removable terminal blocks
(e.g. when exchanging device)
2
Configuration
The device master data file is used to connect the DP interface as DP slave in
the engineering tool for the PROFIBUS master.
The DP interface is configured in the MSS system using the engineering tool
"Modular Safety System ES".
Matching configurations must be carried out in both engineering tools.
Details on configuration can be found in the manual. The manual is available for
download via the internet link stated below.
Technical Data
Rated operational voltage (PELV)
acc. to IEC 61131-2
Total power consumption
Degree of protection
Weight
Dimensions in mm (W x H x D)
Ambient temperature T
a
Storage temperature T
s
LED displays
Off
No power
Green
Device OK
Green flashing
Device is in the start-up phase
Red/green flashing Device defective
Red
Device defective
Off
PROFIBUS bus communication OK
Red
PROFIBUS fault, e.g. wrong PROFIBUS address
(DP interface module has not been addressed)
Red flashing
PROFIBUS parameterization/configuration fault
Off
No general fault
Red
General fault (communication fault to the basic
device, ...)
All LEDs on
Self-test during restart
Flashing: 0.5 Hz (rate 1:1)
Messages on display
RUN
No faults, everything ok
DPXXX
STOP
The application program of the CPU has stopped
DPXXX
Device is in the start-up phase
WAIT
SF
System bus fault or interruption of the communication to the basic device
SB
SF
Device error DP interface
DEV
BF
Bus fault, PROFIBUS DP error
DPXXX
PROFIBUS DP error (configuration fault)
BF
CFG
PROFIBUS DP error (parameterization fault)
BF
PRM
Main menu, selection of a sub menu
MENU
Set PROFIBUS address
XXX
3RK3511-1BA10
3RK3511-2BA10
English
24 V DC ± 15 %
≤100 mA
IP20
approx. 270 g
111/113 x 45 x 124
0 °C to +60 °C
–40 °C to +85 °C
Order No.: 3RK1703-3WB15-1AA1