5.3

Displaying measured values

The measured values are accessed via pushbuttons.
By pressing the appropriate pushbutton several times, further measured values can be displayed within the
selected menu. For additional information, please refer to the corresponding user manual.
Pushbutton
Displays...
I °C
Currents, temperatures (with extension module EEM-TEMP-MA600)
U F
Voltages, frequency
P PF
Power, power factor (PF)
MAX AVG
Maximum values, average values
H
Total harmonic distortion (THD), harmonics
E h
Energy, operating hours
6

Function test

To perform the function test, the device must be connected and ready for operation. The power factor (PF) of
the system must be between 0.6 > PF < 1. If the power factor is not within this range, this function cannot be
used. The connections (without neutral conductors) are checked using the setting 4BL/3BL/2BL/1BL. All con-
nections (with neutral conductors) are checked using the 4NBL and 3NBL setting.
Error
Description
Err 0
No error
Err 1/2/3
Current transformer connection phase 1/phase 2/phase 3
Err 4
Voltage between V1/V2
Err 5
Voltage between V2/V3
Err 6
Voltage between V3/V1
To eliminate Err 1, Err 2, and Err 3, change the order of the current connections. To eliminate Err 4, Err 5, and Err 6,
change the order of the voltage connections of the measuring transducer.
6.1

Calling the function test

Press button:
The test menu is opened when the "test button" is pressed and held down for at least three seconds.
The function test is started automatically if a test has not yet been performed.
104513_en_02
English
PHOENIX CONTACT 11