Error Description

Error
LED is on
Loads are
not supplied
LEDs are
Battery is
empty after
a short time
LED is on
Display
Reason
Battery is low
(Red LED on)
Overcurrent/
Short circuit
of loads (Red
LED is
LED flashing)
flashing
Battery voltage
too high
(>15.5 / 31.0 V)
Battery wires
or battery fuse
damaged,
on
battery has
high resistance
Battery has
low capacity
(Red LED on)
32
Remedy
Load will reconnect
as soon as battery is
recharged.
Switch off all loads.
Remove short
circuit. Controller
will switch on load
automatically after
max 1 minute.
Check if other sources
overcharge the battery.
If not, controller is
damaged.
Check battery wires,
fuses and battery.
Change battery

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis