Herunterladen Inhalt Inhalt Diese Seite drucken

Calpeda EASYMAT Originalbetriebsanleitung Seite 25

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 58
9.2.3. SA – Technical assistance settings
To enter password is required (see paragraph 10.1.)
Description
SA01
SA02
SA03
Pressure PID (Proportional gain)
SA04
Pressure PID (Integral time constant)
SA05
Pressure PID (Derivative time constant)
SA06
Min. run frequency
SA07
Max frequency
SA08
Set point pressure step up
SA09
Pressure step up time
SA10
Pressure step up ramp
SA11
Set point control ramp
SA12
Carrier frequency
SA13
Singlephase starting frequency
SA14
Singlephase starting voltage
SA15
Nominal voltage
9.2.4. MAn – Fixed speed mode activation
To enter password is required (see paragraph 10.1.)
Description
MAn1 Fixed speed mode activation
MAn2 Working frequency [MAn2 ≤ UP03]
a
9.3. Alarms
Displayed alarm
Er01 Blockage due to no water
Er02 Pressure transducer fault
Er03 Blockage due to low supply voltage
Er04 Blockage due to high rectified voltage
Er05 Blockage for memory failure
Er06 Blockage due to overcurrent in the electro
pump motor
Er07 Blockage due to overcurrent in the
frequency converter
Er08 Blockage due to direct short circuit between
the phases of output terminals
Er09 Blockage due to overheating
Er10 Blockage due to overheating of the power module
Er11 Blockage due to low voltage 24 V
Er12 Stop for float switch intervention
Er13 Internal hardware error
Er14 Cascade mode communication error
In case of multiple fault, scroll with the buttons
In case of thermal block it is advised to check the causes that have created the problem before
restart the pump operation.
Standard Modifications Note
2,8
5,5
5,0
(Hz)
30
(Hz)
60
(bar)
0,3
(s)
3
(bar/s)
0,3
(bar/s)
0,4
7010
(Hz)
80
(V)
195
(V)
220
Standard Modifications Note
oFF
(Hz)
45
Causes
The device is in failure due to no water.
The system try to restart automatically.
- One attempt every 10 minutes for 6 times.
- One attempt every hour for 24 times.
- One attempt every 24hours for 30 times.
Not connected cable, broken connection, pressure
transducer spoiled.
Supply voltage lower than 190V.
- The system automatically restart when the clamp
voltage is higher than 190V.
Supply voltage higher than 250V.
- The system automatically restart when the clamp
voltage is lower than 250V.
The system will restart with a delay defined by AP19
from the state variation of the float switch. The control
panel for remote alarm not report this alarm.
Contact the technical assistance
Check the RS 485 connection or that both pumps
are enabled.
(plus) or
(minus) to visualize the fault sequence.
25

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis