EnErgy-saving frEEzE protEction controllEr installation instructions
DEScRIpTION
The RAYSTAT-ECO-01 controller is used to control heat-tracing freeze
protection systems based on ambient temperature. The controller provides
a pilot-duty relay to drive an external contactor.
The controller adjusts the power of the heating cable by energizing the
circuit for a percentage of a complete duty cycle. For example, if the
ambient temperature is halfway between minimum ambient and 40°F
(4°C), the heating cable will be energized for 5 minutes and off for 5
minutes. The actual duty-cycle periods and ratios vary, depending on
ambient temperature.
For technical support, call Pentair Thermal Management at (800) 545-6258.
ELEcTRIcAL cODES
Installation and all wiring must be in accordance with applicable
regulations. The controller must be installed by a qualified electrician and
in nonclassified areas only.
OpERATING ENvIRONMENT
Enclosure:
Polycarbonate, rated NEMA 4X and IP67
Temperature:
–40°F to 125°F (–40°C to 52°C)
Humidity:
5% to 95% relative humidity, noncondensing
WARNING: This controller must be installed properly to ensure
proper operation and to prevent frozen pipes, shock, or fire.
Read and carefully follow all the installation instructions.
TYpIcAL INSTALLATION
Ambient
sensing
RTD
Alarm
relay
output
RAYSTAT-ECO-01
controller
THERMAL MANAGEMENT SOLUTIONS
RAYSTAT-ECO-01
Control output
Dedicated
supply voltage
120/240 Vac
EN-RaychemRayStatEco01-IM-H56071 01/13
SpEcIfIcATIONS
Input power:
100 –240 Vac ± 10%, 50/60 Hz; internal power less
than 5 watts
Maintain temperature: Settable to 40°F or 50°F (4°C or 10°C)
Minimum ambient
Settable from 20°F to –70°F (–7°C to –57°C)
temperature:
Control relay:
SPST, 3 A at 240 Vac
Alarm relay:
SPDT, 0.6 A at 125 Vac, 2 A at 24 Vac/Vdc, switches
on power loss, RTD failure, or temperature alarm
Replaceable fuses:
80-mA transformer fuse
4-A control relay fuse
INSTALLATION MATERIALS/TOOLS (NOT SUppLIED)
• Wall fasteners for mounting: four screws for a 3/16-in (4.5-mm) hole.
pARTS (SUppLIED)
• RAYSTAT-ECO-01 controller
• 100-ohm RTD with 6-ft (2-m) lead
• Gland (black), seal, and locknut for RTD
• Plug-in connectors for RTD and alarm relay
• 3 glands (gray), seals, and locknuts for 0.25–0.5-in (8–13-mm) diameter
cables.
• 2 watertight hole plugs for unused holes
• 2 sets of replaceable fuses
ø 1
ø 2
ø 3
N
Control
contactor
C
Distribution panel
Ground-fault
protection device
Power connection
Heating cable
End seal