Technical Specifications

KNX mains connection:
24 V via KNX bus voltage
Settings:
by means of ETS software, remote control or bus
Lighting channels:
Switching/dimming;
switching mode - constant-lighting control
Light 1 – Light 4
Stay-'ON' time:
IQ mode, 1 – 30 min.,
depending on presence and light level
Light measurement:
Mixed light
Basic brightness :
OFF/ 10% – 50%
Stay-'ON' time:
Basic brightness 'ON' duration, 1 – 30 min.
HVAC output:
depending on presence
Switch-on delay:
Room surveillance, 1 – 30 min.
Stay-'ON' time:
1 – 120 min.
Presence stay-'ON' time output: 1 – 255 sec.
Further outputs:
Light level, scenario-controlled
Square detection zones:
IR Quattro KNX
Presence:
no more than 4 x 4 m (16 sqm)
Radially:
no more than 5 x 5 m (25 sqm)
Tangentially:
no more than 7 x 7 m (49 sqm)
Angle of coverage:
HF 360 KNX
360° with 140° aperture angle
also through glass, wood and
stud walls. 1 or 2
detection directions can be
masked out for adjustment to
the room situation.
Reach:
HF 360 KNX
at most 8 m all-round,
at least 1/3, 2/3,
max. electronically
selectable setting
(ETS software, KNX bus,
remote control RC 6)

Remote Control

Using the PC 7 user remote
Service remote control
control (optional), functions can
RC 6 (optional) permits
be conveniently activated from
convenient configuration
the floor.
(see Accessories on p. 15)
PC PRO KNX_Zentraleuropa.indd 18-19
PC PRO KNX_Zentraleuropa.indd 18-19
IR Quattro HD KNX
no more than 8 x 8 m (64 sqm)
no more than 8 x 8 m (64 sqm)
no more than 20 x 20 m (400
sqm)
DUAL HF KNX
refer to diagram on p. 17
also through glass, wood
and stud walls.
DUAL HF KNX
min., 1/3, 2/3, max.
electronically selectable
setting in either direction
(ETS software, KNX bus,
remote control RC 6)
- 18 -

Troubleshooting

Malfunction
Cause
í No supply voltage
Light does not switch 'ON'
í Twilight level set
too low
í No movement being
detected
í Ambient brightness
Light does not switch 'OFF'
too high for selected light
level
í Stay-'ON' time running out
í Interference from heat
sources (IR sensor only),
e.g.: fan heater, open doors
and windows, pets, light
bulb/halogen floodlight,
moving objects
í Stay-'ON' time too short
Sensor switches 'OFF' in spite
í Light-level threshold too
of persons being present
low
í Stay-'ON' time too long
Sensor does not switch 'OFF'
quickly enough
í Reach is reduced when
Sensor does not switch 'ON'
quickly enough when ap-
approached from the front
proached from the front
too low
í Twilight level set
Sensor does not switch 'ON'
when persons are present in
spite of it being dark
Remedy
í Check supply voltage
í Slowly increase
light threshold level until
light switches 'ON'
í Ensure unobstructed sen-
sor vision
í Check detection zone
í Increase light level
setting
í Wait until stay-'ON' time
elapses; reduce stay-'ON'
time if necessary
í Use stickers to mask out
stationary sources of inter-
ference
í Increase stay-'ON' time
í Change light threshold
í Reduce stay-'ON' time
í Install additional sensors
í Reduce distance between
two sensors
í Sensor deactivated by
switch/button?
í Semi-automatic mode?
í Increase light level
setting
- 19 -