Herunterladen Inhalt Inhalt Diese Seite drucken

System Overview; Installing The Device - Bosch FCS-320-TM Installationsanleitung

Vorschau ausblenden Andere Handbücher für FCS-320-TM:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 11
FCS-320-TM | FCS-320-TM-R

System Overview

Figure 1, Page 4
FCS-320-TM series connections
1
2
3
4
Figure 2, Page 4
FCS-320-TM series displays
1
2
3
4
5

Installing the Device

WARNING!
The equipment may only be installed by authorized and qualified personnel!
Switch off the device before carrying out any connection work!
NOTICE!
-
-
-
-
1.
2.
3.
4.
5.
6.
7.
Bosch Sicherheitssysteme GmbH
Connection for aspiration pipe
Connection for air return pipe
Pre-punched M 25 cable entries for connection to fire panel or auxiliary power supply
(input/output)
Pre-punched M 20 cable entries for connection to fire panel or auxiliary power supply
(input/output)
Operation LED
Main alarm LED
Fault LED
Infrared port
Fire source identification displays for areas A-E
When selecting the installation location, it must be ensured that the device displays are
easily visible.
Remember when planning that the device fans generate a noise level of approx. 40
dB(A).
The air outlet on the unit must not be obstructed. The distance between the air outlet
and adjacent components, e.g. a wall, must be at least 10 cm (4 inches).
The aspirating smoke detector can be installed with the suction device pointing up or
down (to do this, the detection device cover must be rotated through 180°). If the
aspiration pipe points down, make sure no impurities or dripping water enter the air
return pipe, which will be pointing up.
First, clearly mark the fixing points on the installation position provided on the
equipment. To guarantee a safe and low-vibration hold, the housing base must be
secured with four screws (∅ max. 4 mm (0.2 inches)).
Fix the housing base to the surface by means of four screws in accordance with the
mounting type. Make sure that the housing base is not fixed under mechanical tension
and that the screws are not tightened too much. Otherwise, the device might be
damaged or undesirable secondary noise may arise.
Using a screwdriver, carefully punch out the required cable entries from the housing
base.
Carefully fit the cable bushing(s) as required with M20 or M25 cable entries (2 x M20 and
1 x M25 included in the delivery) by inserting them into the corresponding cable entry/
entries.
Punch out the cable entries using a sharp object.
Caution: Do not cut the cable entries with a knife!
Feed the ribbon cable(s) (max. 2,5 mm²) through the prepared M20 or M25 cable entries
into the device and cut to the required length inside the device.
Wire the device according to the connection information described below.
en
19
F.01U.123.590 | 1.0 | 2009.11

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Fcs-320-tm-r

Inhaltsverzeichnis