 Install the flush-mounting box in the correct position – horizontally or vertically aligned
– in the wall. Horizontal installation: Arrow OBEN TOP points upwards. Vertical in-
stallation: Arrow OBEN TOP points to the left. Pull bus and 230 V lines through the
appropriate bushings.
 Connect mains voltage AC 230 V to terminal (7).
 Connect bus line to terminal (8).
Figure 4, installation into a flush-mounting box
 Install the device in flush-mounting box (17). Use enclosed screws (15).
 Attach design frame (16) and press on.
 If applicable, remove protective foil.

5.2 Startup

Downloading the physical address
The device must have been connected and ready for use.
Programming key (10) and LED (9) on the bottom side of the device must be accessible.
Configuration and startup with ETS2 version 1.3a or ETS3.0d.
 Press programming key (10).
The programming LED is illuminated.
 Assign the physical address.
The programming LED (9) ceases to be illuminated.
 Note the physical address on the bottom side of the device.