Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi HC-A8MB Installations- Und Betriebshandbuch Seite 16

Network / modbus gateways
Vorschau ausblenden Andere Handbücher für HC-A8MB:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 31
Operation
Offset (1)
Name
22
OPER_CONDITION
23
(Not used)
AMBIENT TEMPERA-
24
TURE
25
RCS_TEM
26
RCS_CONFIG
27
RCS_GROUP
28~30
(Not used)
31
REM_TEM
N O T E
(1) Register address is calculated as: "N + (Address * 32) + Offset" where:
N: Data table position is 2000, position 20000 is also available to maintain compatibility with old Modbus gateway.
Address: Indoor unit address as configured by configuration software.
(2) These numbers refer to signed 16-bit value using 2-complement format for negative values
(3) Bit 0 (ON/OFF) and Bit 4 (Louver) selectable only when all centrals are actived.
In order to full lock setting from RCS (Central shown in RCS) set this register to 31.
10
Description
Unit operation condition
(Not used)
Ambient temperature (2)
Remote control switch temperature
(only when available in the unit) (2)
Remote control switch configuration
Remote control switch group
(Not used)
Remote sensor temperature (2)
PMML0351A rev.0 - 11/2014
Values
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
(Not used)
-63ºC ~ 63ºC
-63ºC ~ 63ºC
b0: 0 Master/1Slave
b1: 0 wih RCS/1 Without RCS
0: No group
1~255
(Not used)
-63ºC ~ 63ºC
Read/Write
Read
(Not used)
Read
Read
Read/Write
Read/Write
(Not used)
Read

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Hc-a64netHc-a64mb

Inhaltsverzeichnis