HINWEISE
ACP BACnet-BACnet Error Response Table
Error PDU
Reading of the object list during the initialization of
the LG-NET
Request to access to an object not installed.
Request to access to a property not installed.
Request to write to a prohibited area.
Request to write in a format different from the
property.
Request to access to a specified index outside the
array index range.
Request to write a value outside the permissible
range.
A COV registration request of more than 10
registration items.
An Event registration request of more than 10
registration items.
Request for the deletion of an element not existing
in the list.
Request for the execution of the AddListElement/
RemoveListElement for a property that is not of
List type.
Reject PDU
A propertyID or value overflow or underflow occurred
during WritePropertyMultiple operation.
The type of parameter for the execution of the service is
different in type.
An error was detected during tag decoding.
A parameter shortage occurred during the execution of
the service.
Too many arguments for the execution of the service.
An attempt to execute an unsupported service with
confirmation.
Error PDU
Reject PDU
Error Class
Device(0)
Configuration_In_Progress(2)
Object(1)
Unknown_Object(31)
Property(2)
Unknown_Property(32)
Property(2)
Write_Access_Denied(40)
Property(2)
Invalid_Datatype(9)
Property(2)
Invalid_Array_Index(42)
Property(2)
Value_Out_Of_Range(37)
Resource(3)
No_Space_To_Add_List_
Resource(3)
Service(5)
Service(5)
Property_Is_Not_List(22)
Reject Reason
Inconsistent_Parameter(2)
Invalid_Parameter_Data_Type(3)
Invalid_Tag(4)
Missing_Required_Parameter(5)
Too_Many_Arguments(7)
Unrecognized_Service(9)
Error Code
Other(0)
Element(19)
Other(0)