Fault detection and elimination

Malfunction of the drive

Fault
Cause
Motor does not rotate
DC−bus voltage too low
(Red LED is blinking every 0.4 s;
keypad display
Controller inhibited
(Green LED is blinking, keypad display:
Automatic start inhibited (C0142 = 0 or 2)
DC injection brake (DCB) active
Mechanical motor brake is not released
Quick stop (QSP) active (keypad display:
Setpoint = 0
JOG setpoint activated and JOG frequency = 0
Active fault
Wrong parameter set active
Operating mode C0014 = −4−, −5−, but no motor
parameter identification executed
Under C0410 several functions which exclude each
other, are assigned to the same signal source.
Use of internal voltage source X3/20 for function
modules Standard I/O, INTERBUS, PROFIBUS−DP or
LECOM−B (RS485):
Jumper between X3/7 and X3/39 is missing
Motor does not rotate smoothly
Defective motor cable
Maximum current set too low (C0022, C0023)
Motor underexcited or overexcited
C0084, C0087, C0088, C0089, C0090, C0091
and/or C0092 are not adapted to the motor data
Current consumption of motor
Setting of C0016 too high
too high
Setting of C0015 too low
C0084, C0087, C0088, C0089, C0090, C0091
and/or C0092 are not adapted to the motor data
Motor rotates, setpoints are 0"
With the function
has been selected.
150
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Remedy
Check mains voltage
LU
)
Remove the controller inhibit, controller
c
inhibit can be set through several
)
sources
LOW−HIGH edge at X3/28
If necessary, correct start condition
(C0142)
Deactivate DC injection brake
Manual or electrical release of
mechanical motor brake
c
Remove quick stop
)
Select setpoint
Select JOG setpoint (C0037 ... C0039)
Eliminate fault
Change to correct parameter set via
terminal
Motor parameter identification (C0148)
Correct configuration in C0410
Jumper terminals
Check motor cable
Adapt settings to the application
Check parameter setting (C0015, C0016,
C0014)
Manual adaptation or identification of
motor parameters (C0148)
Correct setting
Correct setting
Manual adaptation or identification of
motor parameters (C0148)
j
Set the setpoint to "0" via C0140 = 0
of the keypad a setpoint
EDK82EV113 DE/EN/FR 8.1