Herunterladen Inhalt Inhalt Diese Seite drucken

Safety Instructions; Scope Of Delivery; Installing The Device - Bender CP700 Kurzanleitung

Vorschau ausblenden Andere Handbücher für CP700:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Quickstart "Installation and connection"
CP700
Condition Monitor for Bender BMS devices and universal measuring devices
This reference guide does not replace the operating manual. The manual is available in the download area of our homepage. Make sure that the
personnel has read this manual and understood all instructions relating to safety.

1. Safety instructions

Risk of fatal injury from electric shock!
Parts of the system are live. During installation and con-
nection:
DANGER
Do not touch parts of the system.
Electrically isolate the installation and secure it
against unintentional switch on.
Risk of destruction due to incorrect mains voltage
Refer to nameplate for permissible mains voltage.
WARNING

2. Scope of delivery

You will receive:
• The CP700
• This quickstart guide
• The manuals "CP700" and "COMTRAXX" can be downloaded as
a PDF file at:
http://www.bender.de > Service & support >
Download > Operating manuals
• A pluggable screw terminal for the power supply
• Two RS-485 cables for connection to the BMS bus and the
Modbus RTU, 2 m long
• Two terminating resistors each for the BMS bus and the Mod-
bus RTU
• Four mounting brackets
CP700_D00005_01_Q_DEEN/03.2016
Malfunction due to duplicated addresses!
The duplicate assignment of addresses can cause serious
malfunctions in the bus systems affected.
WARNING
Ensure correct address setting and termination of
the CP700.
Do not remove CompactFlash card
Do not remove the CompactFlash card in order to ensure
that all device properties are available!

3. Installing the device

The CP700 can be installed into control panels and cabinet doors.
Material thickness min./max. = 2 mm/6 mm
1.
Make an installation cut-out of 199 mm x 143 mm and smooth
the rough edges. The surface of the cut-out must be even. An
uneven surface may result in damage to the display.
2.
Insert the mounting brackets into the CP700 and slide them
down (see orange markings in the picture below).
3.
Fasten the screws of the mounting brackets securely (tighten-
ing torque approx. 0.5 Nm).
EN-1

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis