4. Connecting the device

Connection
1.
Plug in the RJ45 cable for connection to the PC or LAN (9)
2.
Plug in the RS-485 cable for connection to the BMS bus (3) and
the Modbus RTU (1). Switch or connect the associated termi-
nating resistors.
3.
Connect the DC 24 V voltage supply, the functional earth (6)
and the earthing connection (7).
BMS bus, Modbus RTU
Two connecting cables (RS-485 cable) are included in the scope of delivery of the CP700. The double cable ends facilitate the connection of the
device if it is arranged in the middle of the bus. Both cables have the same pin assignment.
Plug connector
Bridge 4--9
Bridge 1--6
Not connected
EN-2
10
5
4
Loose cable ends
Core colour
A1
White
A2
Yellow
B1
Brown
B2
Green
Shield
Black
9
8
7
3
2
1
Modbus RTU interface
2
Switch for terminating resistor/bus bias voltage for
Modbus RTU interface.
3
BMS bus (Bender measuring device interface)
4
Switch for BMS bus termination/bus bias voltage.
5
USB interface, is not used
6
Connection of DC 24 V supply voltage
and functional earth
7
Earthing connection
8
USB interfaces, are not used
9
Ethernet 10/100/1000, RJ45 socket for connection to
PC or the local network (hub, switch, router)
10
RS-232 interface, is not used
Connection to the
BMS bus
A
B
Shield
6
1
Connection to the
Modbus
D+
D-
Shield
CP700_D00005_01_Q_DEEN/03.2016