Ceag TLS-BUS-Modul Betriebsanleitung Seite 6

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

T1
T1
TLS - BUS - Modul
400 71 346 965
N
L
N
L
X
X
Service key for testing of the communication between module -
safety lighting via RS 485-BUS
7
8
fig. 1 Connections TLS module
*
*
L2
L3
*
= 3PH
DLS
1
0
3 PH
S485
Out
SE
A
B
fig. 2
Address-
switch 1
Address swtch 1
6
Mounting and Operating Instructions
TLS/3PH-BUS-Module
X
X
K2
K2
K1
K1
max.10A
max.10A
K2
T2
T1
K1
-
24V
+
PE
PE
N
-
-
+
+
+
X
PE
address
2
2 3
3
1
4
0
5
9
6
8
7
B1 B2
X
Address-
switch 2
Address switch 2
0
0
0
1
0
2
...
...
1
0
1
1
...
...
...
...
2
5
2
6
...
...
3
9
X
X
N
N PE
T2 T2
N
PE
(0)
address
1
0
RS485
Out
IN
-
A
SE
A
SE
B
B
Module addresse
not permissible
not permissible
not permissible
cates a malfunction. If several
PE
L
L
modules (max. 25) are operated
in a system, then the RS 485
L
bus and the 24 V supply are
(U)
to be connected in series. The
screen on the BUS cable is to
be connected to the SE termi-
nals using a suitable clamping
2
3
2 3
1
4
arrangement.
5
0
9
6
8
7
A terminating resistor (120 W)
must be fitted at the start and
end of the BUS cable. For this
B1 B2
X
purpose, a jumper is to be fitted
to terminals B1/B2 on the last
module; this activates the built-
in terminating resistor. If the
safety system is at the start of
the bus cable, then the appro-
priate terminating resistor is to
be fitted to terminals provided
for this purpose. The supply for
the switch glow lamps with a
protected mains supply must be
provided from the emergency
lighting system using a separate
changeover circuit (protected
mains).
Addressing
Prior to operation in a CEAG
safety lighting system, the
module address must be set.
For this purpose the required
address (1 - 25) is to be set on
the code switches on the mod-
ule front panel using a suitable
screwdriver (arrow to number,
Figure 2).
1
2
...
10
11
...
...
25
...