b. Function of the button
Duration pressing
button [s]
< 1
1 - 5
5 - 10
10 - 20

6.5 Luminaire monitoring CGLine

The GuideLed luminaires are prepared for connection to the CEAG CG-Controller CGLine 400
or the CEAG CGLine PC-Interface. An individual, distinct identification number (6. characters) is
assigned to every luminaire in the CGLine luminaire series.
This ID number must be transferred to the installation plan for subsequent configuration work.
The removable ID sticker in the luminaire can be used for this.
To the CG-Controller CGLine 400 or the CGLine PC-Interface maximum 4 bus cables (2-core)
with up to 100 luminaires each can be connected. The max. data line length per strand is
0.5 mm
Bus voltage:
Max.voltage drop:
Bus current
An unscreened, 2-core cable with free bus topology can be used as a data cable.
Each of the luminaires connected to the data bus cable is automatically recognised by the CG-
Controller. The CG-Controller can assign a short address to the connected luminaires, which
can be polled via the three LEDs on the luminaire.
For more information regarding addressing please see operating instructions of CG-Controller
CGLine 400 or CGLine PC-Interface.
7. Inspection/Maintenance/Repair
Observe the valid regulations for the inspection, maintenance and repair of electrical equipement!
8. Disposal / Recycling
When disposing of defective devices, comply with valid regulations for recycling and
waste disposal. Plastic parts are marked with corresponding symbols.
The LiIon battery integrated in the luminaire must be returned to the seller or an approved
disposal location and must not be disposed of by the customer, in accordance with the
2006./6.6./EG EU directive.
When returning or disposing of batteries please ensure that these are protected from
short-circuiting and electrical contact with other batteries.
In case of returns you need a RMA - number from us. For further information see
www.ceag.de!
Operating Instructions
GuideLed self contained luminaire
SL 13811 ... 13822 CGLine
Function
Display of emergency operating time
Display of luminaire address
Setting the dim-level
Start function test
Start / stop duration test
Reset of the luminare
: 450m
2
1.0 mm
: 900m
2
22,5VDC
13VDC
400mA
We reserve the right to make techni-
cal alterations without notice!
CEAG Notlichtsysteme GmbH
1.5 mm
: 1300m
2
17