3. Safety Notes

p The luminaire shall only be used for its intended purpose and in an indamaged and perfect
condition!
p Only genuine CEAG spare parts may be used for replacement and repair!
p When working on the emergency luminaire first cut off mains (charging phase and L') and inter-
rupt battery operation.
p Prior to its initial operation, the luminaire will have to be checked in accordance with the
instructions as per section 'Installation'!
p Carry out the marking of the emergency luminaire:
Assign the circuit, the luminaire no. and ID no. and enter them.
p The manual log book shall be performed in compliance with the national regulations. It is not
applicable by automatical log book!
p Any foreign matter shall be removed from the luminaire prior to its initial operation!
p Observe the national safety rules and regulations for prevention of accidents as well as the safe-
ty instructions included in these operating instructions marked with
4. Conformity to standards
Conforms to: EN 60 598-1, EN 60 598-2-22 and DIN EN 1838.
Developed, manufactured and tested in accordance with DIN EN ISO 9001.

5. Technical Data

Input voltage:
Enclosure material:
Colour of enclosure:
Luminous flux phiE/phiNenn at the end
of rated operating time
Supply terminals:
(doubled for through wiring)
Insulation class:
Degree of protection acc. to EN 6.0529: IP 41 (module enclosure IP 20)
Lamp:
Admissible amb. temperature
Weight:
Connection power mains operation:
(apparent power/active power)
Battery:
Operating Instructions
GuideLed self contained luminaire
SL 13811 ... 13822 CGLine
230 V AC, 50 Hz
Lamp: Polycarbonat, aluminium
Module enclosure: Sheet steel
white, similar to RAL 9010
1 h
100%
mains, L, L' and PE up to 2.5 mm²
CGLine bus up to 1.5 mm²
I
HighPower LEDs 2 x 1.6. W
-5°C ... +30°C / maintained mode
0°C ... +35°C / non-maintained mode
13811/13821: 1.01 kg
13812/13822: 0.54 kg
6..9 VA / 6..7 W
Lithium-Ionen 3.7 V / 4000 mAh
with multiple protection circuit
!
3 h
8 h
55%
20%
CEAG Notlichtsysteme GmbH
14