Commissioning and operation
- Remove the CompactFlash card from the unit and insert it into the CompactFlash card
slot in the PC.
2.
Start the provided PC software and add new unit in the PC database:
- Select "Unit -> Display/change unit set-up/add new unit"
- Select "Unit -> Add new unit" in the new window.
- Assign general informations for the new unit. Select "Parameter file from a data source
(e.g. diskette, ATA flash card)". Select "Continue". Select the appropriate parameter file
(*.rpd) from the CompactFlash card. Select "Continue". A summary of the data to the new
unit is indicated. With "OK" the new unit will be registered in the PC data base.
3.
Adjust set up in the provided PC software and save in the associated database:
- Adjust the unit settings.
- Select "Finished -> Store set-up into unit data base". The new set up parameters are saved
in the PC database. Transfer the new set up file to the CompactFlash card in your PC:
select "Finished -> Create set-up data carrier (diskette/ATA flash card)" and select the
suitable CompactFlash card slot.
- Remove the CompactFlash card from the slot in the PC and insert it into the unit.
4.
Read the new set up into one (or more) unit(s):
- In the main menu, select "CompactFlash (CF) functions -> Load set-up from CF". Repeat
this procedure, to set up further units with this parametrization.
"
Caution!
If the set up CompactFlash card is not removed, the measurement data will begin to be saved
after approx. 5 minutes. The set up data is still kept. Please change the CompactFlash card if the
measurement data is not meant to be saved onto this card.
"
Caution!
Correct and safe functioning is only guaranteed with genuine CompactFlash cards of the
manufacturer.
5.4.5 Set up direct at the unit (via unit keyboard)
F
• Press
. The main menu appears.
V
• With
or
• Confirm with
• Use the softkey
Key function in set up
Z
Cancel entries or return to previous screen.
UT
Moves cursor left or right.
VW
Moves bar up or down, changes parameter/sign.
F
: Enter key = selects the highlighted function, starts parameter change.
36
W
select the desired chapter
F
to call up the Help on the entry selected.
Multi Channel Recorder