Herunterladen Inhalt Inhalt Diese Seite drucken

Endress+Hauser Ecograph T RSG30 Bedienungsanleitung Seite 35

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Multi Channel Recorder
!
Note!
In the provided PC software, the USB interface is addressed like a COM port (serial interface).
In the Windows device manager, you can determine the COM port via which the unit can be
addressed. The unit is displayed in the device manager under "Connections (COM and LPT)" as
"ETU00xA (Com x)". The provided PC software supports the COM-ports 1 to 20 (from version
V1.21.2.0), if necessary reduce the allocation accordingly in the Windows equipment manager.
5.4.3 Procedure set up via interface and provided PC software
!
Note!
In order to be able to use this function, the unit must already be registered in the PC database,
and/or register in the PC database at first.
1.
Connect the unit interface (RS232 / RS485, USB or Ethernet) to the PC.
2.
Start the provided PC software and add new unit in the PC database:
- Select "Unit -> Display/change unit set-up/add new unit"
- Select "Unit -> Add new unit" in the new window.
- Assign general informations for the new unit. Select the interface for the unit set up.
Select "Continue". Select the appropriate interface parameters (must agree with the
attitudes to communication on the unit). Select "Continue". A summary of the data to the
new unit is indicated. With "OK" a connection to the unit is made and the new unit will
be registered in the PC data base.
3.
Adjust the unit settings and select "Finished -> Transmit set-up to unit". The new set up
parameters are automatically transferred to the unit.
4.
Finally, the unit settings should be saved in the unit database. Select "Finished -> Store
set-up into unit database".
5.4.4 Set up via CompactFlash card
Save the unit settings on the PC onto the CompactFlash card using the provided PC software.
This set up file can be adopted into the unit if released under "Main menu -> CompactFlash (CF)
functions -> Load set-up from CF".
!
Note!
In order to be able to use this function, the unit must already be registered in the PC database,
and/or register in the PC database at first. In addition a CompactFlash card slot must be present
at the PC.
Procedure set up via CompactFlash card:
1.
Copy set up to CompactFlash card:
- Insert a formatted CompactFlash card into the unit.
- In the main menu, select "CompactFlash (CF) functions -> Copy set-up to CF".
- In the main menu, select "CompactFlash (CF) functions -> Safely remove CF".