Sulzer CP 112 Einstell- Und Belegungsanleitung Seite 9

Control panel type abs
Vorschau ausblenden Andere Handbücher für CP 112:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5
C
P
T
ABS CP 112, A
ONTROL
ANEL
YPE
11
Nominal current P1
6.0 A
Dry run P1
[Off ]
Current alarm delay.
5 s
12
P1 back up start
[Off ]
13
Exercise run P1
[Off ]
14
Leakage monitoring.P1 [Off ]
15
Temperature monitoring.P1 [Off ]
16
Buzzer
[On]
Backlight time.
xx min
Alarm relay [Alarm alert]
Alert on time
10 min
Alert pause time
5 min
C
DJUSTING AND
ONFIGURATION
Table 2 Settings
Enter value
I
from name plate pump
N
Set to nominal current
View only
View only
View only
View only
Leakage monitoring
depending on pump type
if present
[Only message]
Temperature monitoring
for EX pumps is required
if present
[Manual reset]
Alternative with non Ex and existing
temperature monitoring at the pump
[Auto reset]
If no temperature monitoring
present -view only
View only
Enter value, for example. 5 min
Set to 5 min
Alarm relay 1
Selections:
[Alarm alert] = floating alarm contact
[High water] = max. water level
[Active alarm] = only if alarm occurs
View only
View only
G
UIDE
17
Code
[Off ]
Stations ID
CP 112 Ver:
xx.x
8
Mains connection
1
View only
1
View only
View only
ESC
EN