Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Of An Analogue Sensor, For Example A Hsc2-Sensor Including The Appropriate Basic Settings, With Or Without Ex - Sulzer CP 112 Einstell- Und Belegungsanleitung

Control panel type abs
Vorschau ausblenden Andere Handbücher für CP 112:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4
Connection
1
2
3
14
15
16
5
Sensor type
Analogue sensor, for example HSC2
6
Analogue mA1
Scaling 100% =
xx,x m
Scaling 0% = 0,0 m
Units
[m]
Filter 2s
7
Highwater alarm xx,x m
Dry run alarm xx,x m
Identify value of pump pit and register.
EN
2
Connection of an analogue sensor, for example a HSC2-sensor
including the appropriate basic settings, with or without EX.
Pump 1
4
5
6
7
8 9
17
18
19
20
21 22
.
Pump 1
Table 2 Settings
Selection sensor
Enter end value of sensor
turn until value HSC2
correspond, for example 4,0 m.
Set to 4,0 m
View only
View only
View only
High water level 0-3,5 m
Enter value, for example 2 m
Set to 2 m
Dry run limit value
Enter value, for example -3 m
Set to -3 m
8 21 9
F0 F1 Di
Pump 1
1
2
Start level P1
xx,x m
Stop level P1
xx,x m
8
Func. back pressure
[Off ]
9
Start delay.
3s
Stop delay.
xx s
10
Alternative Stop level [Off ]
1
3
5
13
L1
L2
L3
NO
A1
0
A2
2
4
6
14
T1
T2
T3
NO
U1
V1 W1
M
3~
PE
High water level
Start level P1
Lowest switch off point
Stop P1
Start one pump
Enter value, for example 0,7 m
Set to 0,7 m
Stop one pump
Enter value, for example 0,2 m
Set to 0,2 m
View only
View only
Enter Stop delay
Enter value, for example.. 3 s
Set to 3 s
View only