Connection Of A Pressure Pipe Without Compressor (Open System) Including Basic Settings, With Or Without Ex - Sulzer CP 112 Einstell- Und Belegungsanleitung

Control panel type abs
Vorschau ausblenden Andere Handbücher für CP 112:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6
Connection
1
2
3
14
15
16
5
Sensor type
Pressure pipe without compressor
6
Analogue mA1
Scaling 100% =
3,50 m
Scaling 0% = 0,0 m
Units
[m]
Filter
2 s
7
High water alarm
xx,x m
Dry run alarm
xx,x m
Identify value of pump pit and register.
From version 1.7 on fixed, scaling 100% and scaling 0%
will be not shown anymore (see point 18)
EN
3
Connection of a pressure pipe without compressor (open
system) including basic settings, with or without EX.
Pump 1
4
5
6
7
8 9
18
19
20
21 22
17
.
Pump 1
Table 3 Settings
Selection sensor
Change
Int. pressure pipe
View only
View only
View only
View only
Max.water level 0-3.5 m
Enter value for example 2 m
set to 2 m
Dry run limit value
Enter value, for example -3 m
Set to -3 m
1
3
L1
L2
0
2
4
T1
T2
8 21 9
U1
V1 W1
F0 F1 Di
M
3~
Pump 1
Start level P1
xx,x m
Stop level P1
xx,x m
8
Func. back pressure
[Off ]
9
Start delay.
3s
Stop delay.
xxs
5
13
L3
NO
A1
A2
6
14
T3
NO
PE
High water level
Start level P1
Lowest switch off point
/ Stop P1
Start one pump
Enter value, for example 0,7 m
Set to 0,7 m
Stop one pump
Enter value, for example 0,2 m
Set to 0,2 m
View only
View only
Enter stop delay
Value depends on facility and has
to be checked. Make sure that
pump will not suck air.
Pressure pipe has to be free.
Enter value, for example 1s