Connection
1
2
3
14
15
16
In case of using an additional float switch (Normally closed) as max. alarm, pos.13 has to be adapted as follows.
The settings are valid for following level control variations:
- Analogue sensor (HSC2)
- Pressure pipe with or without compressor for air bubbling
- Air bell
Please note that this connection variation is only valid for none Ex pumps.
EN
8
Connection of one float for "back up start" without EX, for high
water (for example with a HSC2 sensor).
Pump 1
4
5
6
7
8 9
17
18
19
20
21 22
.
Pump 1
Table 8 Settings
8 21 9
F0 F1 Di
1
2
3
4
13
P1 back up start
Back up run time
1
3
5
13
L1
L2
L3
NO
A1
0
A2
2
4
6
14
T1
T2
T3
NO
U1
V1 W1
M
3~
PE
Pump 1
High water level
Start level P1
Lowest switch off point
/ Stop P1
[Off ]
Change
P1 back up start
[30 s]
Pumps will stop after xxx sec. after
alarm float switch has switched off.
Value depends on facility
and has to be checked.
Attention:
Make sure that pump will not suck air!
[On]