Step 2: Exemplary setting for parallel mode
In this example, the master is configured according to factory settings.
The slaves do not require setting!
Master
DS-8 Ch. voltage(GEL 14,4V)
DS-7 Ch. voltage(GEL 14,4V)
DS-6 Absorption time (8 h)
DS-5 Adaptive charging (on)
DS-4 Dyn. current limit (off)
DS-3 UPS function (on)
DS-2 Voltage (230V)
DS-1 Frequency (50Hz)
To store the settings after the required values have been set: press the 'Down' button of the master for 2 seconds (lower button
to the right of the DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the 'other settings' can always be recovered.
To start the system: first, turn all devices off. The system will start up as soon as all devices have been turned on.
Step 2: Exemplary setting for 3-phase mode
In this example the leader is configured according to factory settings.
Leader (L1)
DS-8 Ch. Volt. GEL 14,4V
DS-7 Ch. Volt. GEL 14,4V
on
DS-6 Absorption time (8 h)
on
DS-5 Adaptive ch. (on)
on
DS-4 Dyn. current limit (off)
DS-3 UPS function (on)
on
DS-2 Voltage (230V)
on
DS-1 Frequency (50Hz)
on
To store the settings after the required values have been set: press the 'Down' button of the leader for 2 seconds (lower button
to the right of the DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the 'other settings' can always be recovered.
To start the system: first, turn all devices off. The system will start up as soon as all devices have been turned on.

6. MAINTENANCE

The Quattro does not require specific maintenance. It will suffice to check all connections once a year. Avoid moisture and
oil/soot/vapours, and keep the device clean.
22
Slave 1
off
DS-8 na
on
DS-7 na
on
DS-6 na
on
DS-5 na
off
DS-4 na
on
DS-3 na
on
DS-2 na
on
DS-1 na
Follower (L2)
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
off
DS-4 D. c. l. (off)
DS-3 UPS f. (on)
on
DS-2 V (230V)
on
DS-1 na
Slave 2
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 na
DS-1 na
Follower (L3)
DS-8 na
DS-7 na
DS-6 na
DS-5 na
off
DS-4 D. c. l. (off)
DS-3 UPS f. (on)
on
DS-2 V (230V)
on
DS-1 na
off