Warning:
High ground I
The GFCI (Ground Fault Current Interrupter) is active due to a fault current from live parts to the
Explanation:
earth. The inverter will shut down.
Open the circuit breaker, and then disconnect the DC-plugs from the inverter for 5 minutes. After 5
Action:
minutes reconnect DC-plugs and close AC breaker.
If the problem persists, call service.
Warning:
Please Initiate
Explanation:
The inverter has not been initiated for the first time in the factory.
Action:
Call service
Warning:
GFCI Damaged
Explanation:
The GFCI-protection unit is damaged.
Action:
Call service
Warning:
Sensor Damaged
Explanation:
The DC current sensor in the inverter is damaged.
Action:
Call service
Warning:
SCI damaged
Explanation:
The communication between the two micro controllers in the inverter has failed.
Action:
Call service
Warning:
High DC INJ
Normally the inverter injects AC-current into the public grid. When the warning "high DC INJ" is on,
Explanation:
for some reason the injection of DC-current into the grid is higher then acceptable, and the inverter
shuts down.
Open the circuit breaker, and then disconnect the DC-plugs from the inverter for 5 minutes. After 5
Action:
minutes reconnect DC-plugs and close AC breaker.
If the problem persists, call service.
Warning:
High Bus Voltage
Explanation:
The internal BUS-voltage is too high.
Open the circuit breaker, and then disconnect the DC-plugs from the inverter for 5 minutes. After 5
minutes reconnect only the DC-plugs (do not close the circuit-breaker!).
Action:
Is the warning "High Bus Voltage" visible on the display?
Yes
No
Voltage"-warning comes back again after reconnecting to the grid, there is probably something wrong
with the grid. (Call an electrician).
Warning:
Relay Damaged
Explanation:
The internal relays used for connecting the inverter to the grid are damaged.
Action:
Open the circuit breaker.
Call service
Warning:
Auto test failed
Explanation:
The self-test of the inverter has failed. There is an internal failure.
Action:
Open the circuit breaker, and then disconnect the DC-plugs from the inverter for 5 minutes. After 5
minutes reconnect DC-plugs and close AC breaker.
If the problem persists, call service.
Warning:
2.5V Ref Fault
Explanation:
The internal voltage reference of the inverter is defect.
Action:
Call service.
Warning:
There is nothing visible on the display.
Explanation:
The display power is coming from the solar panels.
Action:
Check if the DC-plugs are firmly connected to the inverter. If there is sufficient daylight and the LCD
does not give any indication / value
the voltage from the solar panels is too high, or there is an internal failure (Call service).
close the circuit-breaker and wait for the inverter to reconnect to the grid. If the "High Bus
call service.
11