PERMANENT FAULT (REQUIRING RESET)
BOILER DISPLAY
VIEW
DESCRIPTION OF PERMANENT FAULTS REQUIRING
Group
Specific
code
code
E.00
.04
Return temperature sensor not connected
E.00
.05
Return temperature sensor short-circuited
E.01
.04
Loss of flame detected 5 times in 24 hours (with burner on)
E.01
.11
Incorrect fan speed
Temperature measured by return sensor greater than flow
E.01
.12
temperature
E.01
.17
No circulation of water (permanent)
E.01
.20
Maximum fume temperature value reached
E.02
.00
Boiler resetting
E.02
.07
Low pressure in heating circuit (permanent)
E.02
.16
Communication with boiler board internal memory timeout
Permanent loss of communication between gas valve and
E.02
.17
boiler board
E.02
.19
Dip-switch status change j=1 (paragraph 6.6.1)
E.02
.20
Dip-switch status change j=2 (paragraph 6.6.1)
E.02
.21
Dip-switch status change j=3 (paragraph 6.6.1)
E.02
.47
Connection with external device failed
E.02
.48
Configuration of external device failed
E.04
.00
Gas valve fault
E.04
.01
Flow temperature sensor short-circuited
E.04
.02
Flow temperature sensor not connected
E.04
.03
Maximum flow temperature exceeded
RESET
15
CAUSE
Check / Solution
SENSOR/CONNECTION ERROR
Check the operation of the temperature sensor
Check the sensor/board connection
SENSOR/CONNECTION ERROR
Check the operation of the sensor
Check the sensor/board connection
GAS SUPPLY
Check the gas supply pressure
Check the gas valve calibration
Check the fume exhaust and air discharge terminal
Check the power supply voltage
BOARD/FAN ERROR
Change the air-gas unit
SENSOR/CONNECTION ERROR
Check the sensors for inverted position
Check that the flow sensor is in the correct position
Check the boiler return temperature
Check the operation of the sensors
INSUFFICIENT CIRCULATION
Check the system pressure
Activate a manual vent cycle
Check the operation of the pump
Check the boiler/system circulation
SENSOR ERROR
Check the operation of the temperature sensors
Check the connection of the temperature sensors
FUME SIDE EXCHANGER OBSTRUCTED
Check that the exchanger is clean
DISPLAY OF CURRENT RESET
Wait for the reset to be completed
Check the system pressure and restore
Check the expansion vessel pressure
Check the boiler/system for leaks
MAIN BOARD ERROR
Check for electromagnetic interferences
Replace the main board
MAIN BOARD ERROR
Check for electromagnetic interferences
Replace the main board
BOILER CONFIGURATION CHANGE
Press reset for approx. 2 seconds
BOILER CONFIGURATION CHANGE
Press reset for approx. 2 seconds
BOILER CONFIGURATION CHANGE
Press reset for approx. 2 seconds
ELECTRIC CONNECTION ERROR
Check the X14-A / X12-B connection
Replace the electric connection card
Check the instructions of the external device
MAIN BOARD ERROR
Replace the main board
SENSOR/CONNECTION ERROR
Check the sensor/board connection
Check the operation of the sensor
SENSOR/CONNECTION ERROR
Check the sensor/board connection
Check the operation of the sensor
INSUFFICIENT CIRCULATION
Check the boiler/system circulation
Activate a manual vent cycle
Check the operation of the sensors
7679406 (01-05/17)