CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the roof
α α α α
15°
30°
45°
60°

6. CONNECTION TO THE CHIMNEY

For safety reasons the door of the appliances with constructive system 1, must be opened only for the
loading of the fuel or for removing the ashes, while during the operation and the rest, the door of the hearth
must remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open
door is allowed under supervision.
The stove is endowed with an upper exhaust pipe. The connection pipe to the flue must be the shortest
possible, right, tight and according to the current regulations.
The connection to the chimney must be performed with stable and strong pipes (we recommend a
thickness of 2 mm). The pipe for smokes exhaust must be fixed hermetically to the chimney. The diameter
inside the connection pipe must correspond to the external diameter of the smokes exhaust small trunk of
the stove. This is ensured by pipes according to DIN 1298.
ATTENTION: Eventual flammable pieces in the area of 20 cm's round the
connection pipes must be changed with fireproof and not sensitive to heat
materials.
For a good operation of the equipment it is essential that in the installation place
it is introduced sufficient air for combustion (see chapt. 7).
The depression on the chimney should be 12 Pascal (=1,2 mm of water
column). The measurement must be done always with the equipment hot (rating
calorific value). When the depression exceeds 17 PA (1.7mm of water column)
it is necessary to reduce the same with the installation of an additional flue
adjuster (butterfly valve) on the exhaust pipe or in the chimney.
For safety reasons the door of the stove must be opened only for the loading of
the fuel or for removing the ashes, while during the operation and the rest, the
door of the hearth must remain closed.
IMPORTANT: In order to increase the yield of the stove JUNIOR, it is
possible to ask for a device to be filled in the smoke pipe exhaust , as
indicated in the Picture 8 pos.A.
22
Distance between the roof ridge and the
stack
A (m)
< 1,85 m
> 1,85 m
< 1,50 m
> 1,50 m
< 1,30 m
> 1,30 m
< 1,20 m
> 1,20 m
Chimney stove MAJOR / MINOR – MAX / JUNIOR
Instructions for installation, use and maintenance – EN – Rev.04
UNI 10683/98
Minimum height of the stack
(measured from the outlet )
H (m)
0,50 m
above the roof ridge
1,00 m
from the roof
0,50 m
above the roof ridge
1,30 m
from the roof
0,50 m
above the roof ridge
2,00 m
from the roof
0,50 m
above the roof ridge
2,60 m
from the roof
A
Picture 8