6. Specifications

MODEL
CAPACITY*
INPUT
Low Line Loss
EN
Voltage Range
Low Line Comeback
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Transfer Time
Inverter
EFFICIENCY
AC mode
Battery Mode
BATTERY
Type & Numbers
Recharge Time
Standard
Model
Charging Current
Charging Voltage
Type
Numbers
Long-run
Model
Charging Current
Charging Voltage
PHYSICAL
Dimension,DXWXH(mm)
Standard
Model
Net Weight (kgs)
Dimension, DXWXH(mm)
Long-run
Model
Net Weight (kgs)
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
100%~110%: 30min; 110%~130%: 5min; >130% : 10sec
100%~110%: 3min; 110%~130%: 30sec; >130% : 10sec
Battery
Bypass
Max.: 1A, 2A, 4A, 6A (Adjustable, 6A is only available for 16pcs batteries)
(battery life cycle will be shorten when temperature is above 25°C)
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and
Power management from SNMP manager and web browser
PowerWalker VFI 6000CRM LCD
6000 VA / 4800 W
110 VAC ± 3 % at 50% Load;
176 VAC ± 3 % at 100% Load
Low Line Loss Voltage + 10V
300 VAC ± 3 %
High Line Loss Voltage - 10V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Single phase with ground
≧ 0.99 at 100% Load
208/220/230/240VAC
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
3:1 max
≦ 3 % THD (Linear Load)
≦ 5 % THD (Non-linear Load)
0 ms
0 ms
> 92%
> 90%
12 V / 9 Ah x 16
9 hours recover to 90% capacity
Default : 1 A ± 10%
Max.: 1A, 2A (Adjustable)
218.4V ± 1%
Depending on applications
16 – 20 (Adjustable)
Default: 4 A ± 10%
218.4V ± 1% (Based on 16pcs batteries)
UPS unit: 500 x 438 x 88 [2U]
Battery pack: 668 x 438 x 88 [2U]
UPS unit: 15
Battery pack: 48
500 x 438 x 88 [2U]
15
0 ~ 50°C
<95 % and non-condensing
<1000m
Less than 55dB @ 1 Meter
MAC
24

Werbung