Siemens 6EP1931-2EC21 Betriebsanleitung Seite 6

Vorschau ausblenden Andere Handbücher für 6EP1931-2EC21:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Signaling
"Normal operation",
i.e. the input voltage at the DC-UPS module is higher than the set cut-in threshold. The loads are being supplied by the line-side power supply.
If a battery module is connected, it is fully charged. In normal operation, the green LED (o.k.) is illuminated and relay contact X2.2 – X2.3 (o.k.) is closed.
">85% charge",
i.e. battery is loaded more than 85%. The second green LED (Bat>85%) is illuminated and relay contact X2.7 – X2.8 is closed. . (second green LED
off and relay contact X2.7 – X2.8 open (de-energized position when unit is disconnected) means : Bat<85%, i.e. battery charge below 85%)
"Floating operation",
i.e. the input voltage is lower than the set cut-in threshold. The loads are being supplied by the battery module. In floating operation, the
yellow LED (Bat) is illuminated and relay contact X2.1 – X2.2 (Bat) closed (de-energized position when unit is disconnected).
Alarm signal "Battery not ready":
(de-energized position when unit is disconnected). Causes for the "battery not ready" state in normal operation are as follows: "OFF" operating state, no battery module
connected, reversed polarity or defective battery (battery voltage < 18.5V) or open circuit between battery and UPS module. The interval for polling the operating states
ON/OFF, reversed polariy, defective battery or no battery module connected, open circuit between battery and UPS module, and for activating the relevant signal output
is 20 s during normal operation. After the end of the failure the signal remains till to the next polling.
If the signal flashes in a 2s cycle, this indicates that the battery is defective, but still capable of floating operation. The specified buffering times cannot be kept in such
cases. The battery module must be replaced.
The "Alarm" signal in floating operation means that the battery voltage has dropped to <20.4V and automatic disconnection to protect the battery is imminent. When
the battery has been disconnected due to overload, short circuit, exhaustive discharge protection or buffering timeout, the red LED (Alarm) goes out, but relay contact
X2.4 – X2.5 remains closed. Load rating of relay contacts: 60V DC / 1A or 30V AC / 1A
Interface
: With module type 6EP1931-2EC31, the signals are additionally outputs via a PC-capable serial interface.
They are each displayed in the shape of 5 characters of plain text. The assignment is shown in the table on the right.
When the battery is defective, the signal "Battery ready / not ready" is displayed alternately in a 0.25Hz cycle with a
duty cycle of 0.5. A tool for reading out and processing the signals is available free of charge on the Internet at
http://www.ad.siemens.de/sitop. This website also contains further information about the interface.
Technical specification: 8N1 transmit and receiving, 9600 baud, 8 data bits, 1 stop bit, no parity bit, signal state output
every 84ms ± 20%; data output 29ms ± 20%, pause 55ms ± 20%.PC-interface has to be safety separated according to
EN 60950. The connection to the PC is made by means of a continuous 9-way SUB-D extension lead, (plug/socket),
although only 3 pins are needed. (Pin2, Pin3, Pin7)
Transmit data: Pin2: RXD (data line, acc. to Pin3 of a 25-way plug/socket); Pin3: TDX (neg. supply for the interface,
acc. to Pin2 of a 25-way plug/socket); Pin7: RTS (pos. supply for the interface and at the same time data input line for
the remote signal, acc. to Pin4 of a 25-way plug/socket).
Receiving data: Pin7 (acc. to Pin4 of a 25-way plug/socket): Signal Remote Timerstart. The timer of the UPS module is
started with the set buffering time (table 2) (only with setting "max. time" and "disconnection"). After the set buffering
time the floating operation ends or the output voltage will be disconnected. Sequence of the necessary remote signal
see diagram1 (page 8), generated by On and Off of the supply voltage.
USB:
With module type 6EP1931-2EC41, the signals are output additionally via a PC-capable USB interface. They are each displayed in the shape of 5 characters of
plain text. The assignment is shown in the table above. A tool for reading out and processing the signals is available free of charge on the Internet at
http://www.ad.siemens.de/sitop. This website also contains further information about the interface.
Technical specification: The USB interface is according to specification 2.0, the communication runs only with full speed, i.e. 12Mbit/s. The Interface will be supplied by
the DC-UPS with +5V ("self-powered"), signal state output every 75ms ± 20%; data output 29ms ± 20%, pause 46ms ± 20%. The connection to the PC is made by
means of a usual 4-wired shielded USB-cable with a wave-resistance of 90Ohm, a USB Series"A" connector to the PC and a USB Series "B" connector to the DC-UPS
module and a maximum length of 5m. The cable contains two 28 to 20 AWG "non-twisted" USB-supply wires (VBUS and GND) and two 28 AWG "twisted pair" data
wires (D+ and D-).
Pin assignment: Pin1: VBUS (+4.4V to +5.25V DC), transmit data on Pin2 (D-) and Pin3 (D+), Pin4: GND
Receiving data: Receive of the character "R" (Signal Remote Timerstart) starts the timer of the DC-UPS module with the set buffering time (table 2) (only with setting
"max. time" and "disconnection"). After the set buffering time the floating operation ends or the output voltage will be disconnected.
Environment
Operating conditions acc. to EN 60721-3-3, climate model 3K3 (relative air
humidity 5% to 85%, absolute air humidity 1 g/m
Stationary operation, weather protected, pollution degree 2
Temperature for storage and shipment:
Temperature for operation:
Weight
6EP1931-2EC21
0.4kg
6EP1931-2EC31/41
0.45kg
Installation Instructions
In order to guarantee effective cooling, the unit must be vertically installed such that the input and output terminals are at the bottom. A clearance of at least 50 mm must
be left above and below the unit.
Before commencing with the installation or any repair work, switch off the plant main switch and lock it in the "OFF" position. Please read the operating
instructions for SITOP power.
The fuse on the battery module must be removed before any work is carried out.
Connection and Terminal Assignments
Terminals
Function
X1.1
Input voltage DC 24V
X1.3, X1.5
Output voltage DC 24V
X1.2/X1.4, X1.6
Input/output voltage DC 0V
X1.7/X1.8
Battery module DC 24V
X2.1,2,3
Signal: Normal operation / Floating operation
X2.4,5,6
Signal: Battery not ready / ready
X2.7,8
Signal: charge >85%
X2.9/X2.10
On/Off jumper (no jumper =Off)
X3
Serial interface or USB-interface
!
CAUTION
The external circuitry of all terminals (including signaling and status contacts) must meet the safety requirements stipulated by
VDE 0805 (EN 60950): SELV.
Siemens AG Österreich, 05/2004
When the "Battery not ready" signal is active, the red LED (Alarm) is illuminated and relay contact X2.4 – X2.5 (Alarm) closed
3
3
to 25 g/m
, no condensation)
-40 to +70°C
0 to +60°C
Cable cross-
section
1.0 ... 4mm
17...11 AWG
0.5... 2.5mm
20...13 AWG
Standards
Degree of protection: IP20 to EN60529 (VDE 0470 Part1)
Protection class III to EN60950
VDE 0100 Part 410 (IEC 364-4-41)
VDE 0106 Part 1 (IEC 536)
VDE 0113 Part 1 (EN 60204-1)
IEC 1131; UL 508 / CSA C22.2 File E197259
RI suppression to EN55022, limit-value curve B
Interference immunity to EN 50082-2 incl. Table A2,A3
Cable length
Comments
2
up to 2m
Screw-type terminals for screwdriver with
4.5mm blade width
up to 2.5m
Recommended tightening torque 0.7-0.9Nm
2
up to 3m
Screw-type terminals for screwdriver with
up to 3m
3.5mm blade width
up to 3m
Recommended tightening torque 0.5-0.7Nm
See description above
6 of 8
English
Signal
Text
Battery ready
BUFRD
Battery not ready
ALARM
Normal operation
DC_OK
Not normal operation
DC_LO
Not floating operation
*****
Floating operation
*BAT*
>85% charge
BA>85
<85% charge
BA<85
SITOP DC-USV-Modul 15