selecting oPerAtion Mode
coMFort
The thermostat operates continuously. The
thermostat keeps the selected maintain temperature
of 55°C, 50°C or 45°C as long as the power output of
the connected HWAT heating cable is sufficient.
eco Mode
This mode is developed in order to minimize the
energy consumption in times of few or no tap
activities, mainly during the night. The Eco Mode
reduces the maintain temperature to 50°C for a
defined time duration.
Factory settings values :
Eco mode starting time: 23:00
Eco mode duration: 6 hours
These values can be edited in the parameter
settings.
The Eco Mode can be activated at any time but it is
only active if the selected maintain temperature is
>= 55°C to ensure minimum maintain temperature
of 50°C. It will be indicated by a blinking red light.
oFF Mode
The thermostat will switch OFF the heating cable.
Thermal Building SoluTionS