Advanced menu overview
Menu item
ADVANCED SETTINGS
SENSOR
VENTILATION
TEMPERATURE.
PROFILE
TEMPERATURE.UNIT
SEASON DETECTION
RF PAIRING
RESET.TO.INSTALLER.
DEFAULTS
32
Function
Demand.control.ventilation.based.on.the.built-in.sensors.within.
the.HRU..The.following.functions.can.be.set:.
. PASSIVE.TEMPERATURE
. ACTIVE.TEMPERATURE
. COMFORT.HUMIDITY
. PROTECTION.HUMIDITY
■ ON:.to.set.the.selected.function.to.be.permanently.active.
■ . A UTO.ONLY:.to.set.the.unit.to.only.activate.the.selected.
function.when.it.is.in.AUTO.mode.
■ OFF: to set the unit to never activate the selected function.
See.HRU.manual.
To.set.the.settings.of.the.temperature.profile.
■ ADAPTIVE: The desired indoor temperature to which the unit will
adjust the heat recovery control varies with the outdoor climate
(adaptive.comfort.technology)..The.set.temperature.can.be.
increased.or.decreased.with.1.5°C.from.the.average.setting.by.
selecting.the.WARM.or.COOL.temperature.profile;.(default.setting).
■ FIXED:.The.desired.indoor.temperature.to.which.the.unit.will.
adjust.the.heat.recovery.control.is.fixed.and.does.not.depend.on.
the.outdoor.climate..The.set.temperatures.can.be.changed.in.
FIXED.PRESETS.for.each.temperature.profile.
■ WARM:.set.the.temperature.for.the.temperature.profile.
mode.WARM.in.FIXED.mode;.(Default.=.24°C.or.76°F).
■ NORMAL:.set.the.temperature.for.the.temperature.profile.
mode.NORMAL.in.FIXED.mode;.(Default.=.20°C.or.68°F).
■ COOL:.set.the.temperature.for.the.temperature.profile.mode.
COOL.in.FIXED.mode..(Default.=.18°C.or.64°F).
Set.the.temperature.display.to.°C.or.°F.
To.adjust.the.season.detection.for.bypass.
■ HEAT.UNTIL.RMOT:.To.set.a.RMOT..limit.to.prevent.the.HRU.
from counteracting the effect of the central heating system.
■ COOL.ABOVE.RMOT:.To.set.a.RMOT.limit.to.prevent.the.HRU.
from counteracting the effect of the air conditioning.
To connect an RF device.
■ START: Starts the RF pairing procedure. When multiple
ComfoSense.C.devices.are.used,.one.should.be.chosen.to.
act.as.RF-bridge.to.connect.the.RF.sensors.to.
■ DEL:.Deletes.the.currently.paired.RF.devices.
■ RESET: All settings mentioned in this document except BASIC
SETTINGS,.RF.PAIRING,.RF.ON/OFF.will.be.reset.to.their.default.
values.