ISP-EMIL -120 LSN Expansion Module
Connections
6.
Connection of conventional detectors and wall tamper contact (optional): see Fig. 6, page 12
a.
Incoming and outgoing LSNs may be exchanged. The cable screen must be routed both ways.
b.
When connecting the optional wall tamper contact, remove WT bridge (57 + 58).
If the wall tamper contact is not connected, the WT bridge (57 + 58) remains plugged in.
c.
A maximum of 20 detectors of the same type can be connected to a primary line (VdS).
Loop in terminal resistance after the last detector.
d.
Open collector, 0 V is switched.
e.
Open collector, 12 V is switched.
7.
Connection variants for primary lines PL 1 - PL 6: see Fig. 7, page 12
a.
Emergency line with terminal resistance 12k1
b.
Contact line without terminal resistance
c.
Emergency line with double terminal resistance 12k1
8.
Connection of an arming device (e.g. NBS 10) and associated system components: see Fig. 8, page 13
a.
Incoming and outgoing LSNs may be exchanged. The cable shield must be routed both ways
for loop formation.
b.
Cable shield (wire color: 10 = white/green and brown/green)
c.
Block-type lock display LED1 "BLL" (wire color: 11 = red, 12 = pink)
d.
Block-type lock display LED2 "BLA" (wire color: 13 = green, 14 = gray)
e.
Block-type lock magnet "BSM" (wire color: 17 = yellow, 18 = blue/red)
f.
Block-type lock for tamper detector zone (wire color: 49 = white, 50 = brown)
g.
e.g. coded arming device
h.
Block-type lock for primary line (wire color: 39 = black, 40 = blue)
i.
e.g. door contact
j.
e.g. bolt contact
9.
Connection of line-fed glass break detector: see Fig. 9, page 14
a.
Incoming and outgoing LSNs may be exchanged. The cable screen must be routed both ways.
b.
A maximum of 20 glass break detectors can be connected to a primary line PL 5 and PL 6 (VdS).
Loop in terminal resistance after the last detector. A maximum of 3 detectors are supported
in the event of an alarm. Standby current <1 µA, alarm current max. 4 mA at 6 V
10. Connection of optional IMS-RM relay module: see Fig. 10, page 14
a.
Relay 1 gate input (activation of control output S1 - S4)
b.
Relay 2 gate input (activation of control output S1 - S4)
c.
Relay 1 switch contacts
d.
Relay 2 switch contacts
Bosch Sicherheitssysteme GmbH
Installation manual
| en
21
F.01U.076.548 | V3 | 2008.10