Password = 2001
Level 2
2.1 External VT or CT ratio
Ct =
External primary/secondary CT ratio
Ct =
Selection in the field 1...9999
(max. primary current CT 50kA/5A – 10kA/1A)
Vt =
External primary/secondary VT ratio
Vt =
Selection in the field 1,00...10,00
For voltage direct connection (without external VT) load
By modifying the Ct and/or Vt ratios, the kWh meters are automatically
reset
Password = 3002
Level 3
3.0 Communication protocols
01/16 10783510 WEB E cod.MF9600.
(ex. TA 800/5A
Vt
= 160)
(ex. TV 600/100V
Vt
= 6)
(max. primary voltage TV 1200V)
Vt
=1,00
(See point 3 page 19)
Phase sequence diagnostic
In the software of the device we have added a specific functionality to detect and correct
many problems concerning voltage and / or current connection.
This function can be activated through password and allows to display and modify the
connection sequence provided that the following conditions are respected:
1) The neutral wire (in a 4-wire network) is connected to the right terminal
2) No crossings between cables connected to CT's
nals 1 and 3 - are connected some way both to CT1 and CT2)
3) The power factor is between 1 and 0,5 - Inductive load - for each phase.
See www.imeitaly.com "TECHNICAL SUPPORT"
Nemo 96 HD
(normally number 1)
(e.g. avoid that on phase 1 of the meter-termi-
.
.
5