Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Location; Installing The Indoor Unit - Mitsubishi Electric Mr. SLIM PCA-RP-HAQ Installationshandbuch

Air-conditioners
Vorschau ausblenden Andere Handbücher für Mr. SLIM PCA-RP-HAQ:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 13

2. Installation location

Fig. 2-1

3. Installing the indoor unit

1
2
@
4
5
7
8
(PAC-SG38KF-E)
Fig. 3-1
1)
2)
A Independent piece (Removable)
B Drain tubing
C Gas tubing
D Liquid tubing
E T.B.box
Fig. 3-2
Fig. 3-3
A
B
Fig. 3-4
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and mainte-
nance.
Models
RP71
RP125
Warning:
Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.
∗ More than 300 mm recommended for easy maintenance.
F Obstacle
3.1. Check the indoor unit accessories (Fig. 3-1)
3
The indoor unit should be supplied with the following spare parts and accessories
(contained in the inside of the intake grille).
1
6
2
3
4
5
6
9
7
8
9
(mm)
3.2. Preparation for installation (Fig. 3-2)
1) Suspension bolt installing spacing
2) Refrigerant and drain tubing location
3) Selection of suspension bolts and tubing positions (Fig. 3-3)
(mm)
Using the pattern paper provided for installation, select proper positions for suspen-
sion bolts and tubing and prepare relative holes.
A Pattern paper
B Suspension bolt hole
C Indoor unit width
A Use inserts of 100 kg to
Secure the suspension bolts or use angle stock braces or square timbers for bolt
150 kg each.
installation. (Fig. 3-4)
B Use suspension bolts of
W3/8 or M10 in size
W
D
H
1136
650
296
1520
650
296
Accessory name
Washer
4 pcs + 4 pcs (with insulation)
Pipe cover
1 pc
Pipe cover
1 pc
Band
4 pcs
Drain hose
1 pc
Band
2 pcs
Drain tubing cover
1 pc
Filter element
12 pcs
RP125
1 (ø19.05)
Flare nut
RP71
0
(mm)
Models
A
B
RP71
1180
1136
RP125
1564
1520
(mm)
Models
C
RP71
542
RP125
422
(mm)
A
B
C
E
Min. 100
Min. 100
Min. 500
Max. 250
Min. 100
Min. 100
Min. 500
Max. 250
Q'ty
Large size (For gas tubing)
Small size (For liquid tubing)
3