3. Installation location
Fig. 3-5
Fig. 3-9
Fig. 3-12
Fig. 3-15
3.4.2. When installing a single outdoor unit
Minimum dimensions are as follows, except for Max., meaning Maximum dimensions,
indicated.
Refer to the figures for each case.
1 Obstacles at rear only (Fig. 3-5)
2 Obstacles at rear and above only (Fig. 3-6)
3 Obstacles at rear and sides only (Fig. 3-7)
4 Obstacles at front only (Fig. 3-8)
∗ When using an optional air outlet guide, the clearance is 500 mm or more.
5 Obstacles at front and rear only (Fig. 3-9)
∗ When using an optional air outlet guide, the clearance is 500 mm or more.
6 Obstacles at rear, sides, and above only (Fig. 3-10)
• Do not install the optional air outlet guides for upward airflow.
Fig. 3-6
Fig. 3-10
Fig. 3-13
Fig. 3-16
3.4.3. When installing multiple outdoor units
Leave 10 mm space or more between the units.
1 Obstacles at rear only (Fig. 3-11)
2 Obstacles at rear and above only (Fig. 3-12)
• No more than three units must be installed side by side. In addition, leave space as shown.
• Do not install the optional air outlet guides for upward airflow.
3 Obstacles at front only (Fig. 3-13)
∗ When using an optional air outlet guide, the clearance is 1000 mm or more.
4 Obstacles at front and rear only (Fig. 3-14)
∗ When using an optional air outlet guide, the clearance is 1000 mm or more.
5 Single parallel unit arrangement (Fig. 3-15)
∗ When using an optional air outlet guide installed for upward airflow, the clearance is 1000
mm or more.
6 Multiple parallel unit arrangement (Fig. 3-16)
∗ When using an optional air outlet guide installed for upward airflow, the clearance is 1500
mm or more.
7 Stacked unit arrangement (Fig. 3-17)
• The units can be stacked up to two units high.
• No more than two stacked units must be installed side by side. In addition, leave space as shown.