Herunterladen Inhalt Inhalt Diese Seite drucken

Mitsubishi Electric Mr. Slim PUHZ-RP200YHA2 Installationshandbuch Seite 6

Air-conditioners
Vorschau ausblenden Andere Handbücher für Mr. Slim PUHZ-RP200YHA2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 13
4. Installing the refrigerant piping
Fig. 4-4
A Stop valve <Liquid side>
B Stop valve <Gas side>
C Service port
D Open/Close section
E Local pipe
F Seal section
(Seal the end of the heat insulation
material at the pipe connection section
with whatever seal material you have on
hand so that water does not infiltrate the
heat insulation material.)
Fig. 4-5
(1)
Fig. 4-6
A Valve
I Double spanner section
B Unit side
( Do not apply a spanner other than to this section. Doing
so would cause coolant leaks.)
C Operation section
J Seal section
D Cap
( Seal the end of the heat insulation material at the pipe con-
E Local pipe side
nection section with whatever seal material you have on hand
F Pipe cover
so that water does not infiltrate the heat insulation material.)
G Service port
K Handle
H Wrench hole
4.6. Addition of refrigerant (Fig. 4-8)
• Additional charging is not necessary for this unit if the pipe length does not ex-
ceed 30 m.
• If the pipe length exceeds 30 m, charge the unit with additional R410A refrigerant
according to the permitted pipe lengths in the chart below.
* When the unit is stopped, charge the unit with the additional refrigerant
through the liquid stop valve after the pipe extensions and indoor unit have
been vacuumized.
When the unit is operating, add refrigerant to the gas check valve using a
safety charger. Do not add liquid refrigerant directly to the check valve.
6
A Front piping cover
B Piping cover
C Stop valve
D Service panel
E Bend radius : 100 mm-150 mm
G Pipe cover
H Do not use a wrench here.
Refrigerant leakage may result.
I Double spanner section
(Do not apply a spanner other than to
this section. Doing so would cause cool-
ant leaks.)
(2)
Fig. 4-7
4.3. Refrigerant piping (Fig. 4-4)
Remove the service panel D (three screws) and the front piping cover A (two
screws) and rear piping cover B (two screws).
1 Perform refrigerant piping connections for the indoor/outdoor unit when the out-
door unit's stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping.
3 After connecting the refrigerant pipes, check the connected pipes and the in-
door unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)
4 A high-performance vacuum pump is used at the stop valve service port to
maintain a vacuum for an adequate time (at least one hour after reaching –
101 kPa (5 Torr)) in order to vacuum dry the inside of the pipes. Always check
the degree of vacuum at the gauge manifold. If there is any moisture left in the
pipe, the degree of vacuum is sometimes not reached with short-time vacuum
application.
After vacuum drying, completely open the stop valves (both liquid and gas) for
the outdoor unit. This completely links the indoor and outdoor coolant circuits.
• If the vacuum drying is inadequate, air and water vapor remain in the coolant
circuits and can cause abnormal rise of high pressure, abnormal drop of low
pressure, deterioration of the freezing machine oil due to moisture, etc.
• If the stop valves are left closed and the unit is operated, the compressor and
control valves will be damaged.
• Use a leak detector or soapy water to check for gas leaks at the pipe connec-
tion sections of the outdoor unit.
• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct
torque: 20 to 25 N·m (200 to 250 kgf·cm).
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.
5 Use sealant to seal the ends of the pipe cover around the pipe connection sec-
tions to prevent water from entering the thermal insulation.
4.4. Refrigerant pipe airtight testing method (Fig. 4-5)
(1) Connect the testing tools.
• Make sure the stop valves A B are closed and do not open them.
• Add pressure to the refrigerant lines through the service port C of the liquid
stop valve A .
(2) Do not add pressure to the specified pressure all at once; add pressure little by little.
1 Pressurize to 0.5 MPa (5 kgf/cm
pressure does not decrease.
2 Pressurize to 1.5 MPa (15 kgf/cm
pressure does not decrease.
3 Pressurize to 3.6 MPa (36 kgf/cm
2
kgf/cm
G) for the RP250 and measure the surrounding temperature and
refrigerant pressure.
(3) If the specified pressure holds for about one day and does not decrease, the
pipes have passed the test and there are no leaks.
• If the surrounding temperature changes by 1°C, the pressure will change by
2
about 0.01 MPa (0.1 kgf/cm
G). Make the necessary corrections.
(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the
source of the gas leak.
4.5. Stop valve opening method
The stop valve opening method varies according to the outdoor unit model. Use
the appropriate method to open the stop valves.
(1) Liquid side of stop valve (Fig. 4-6)
1 Remove the cap and turn the valve rod counterclockwise as far as it will go with
the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.
(Approximately 10 revolutions)
2 Make sure that the stop valve is open completely and rotate the cap back to its
original position.
(2) Gas side of stop valve (Fig. 4-7)
1 Remove the cap, pull the handle toward you and rotate 1/4 turn in a counter-
clockwise direction to open.
2 Make sure that the stop valve is open completely, push in the handle and rotate
the cap back to its original position.
Refrigerant pipes are protectively wrapped
• The pipes can be protectively wrapped up to a diameter of ø90 before or after
connecting the pipes. Cut out the knockout in the pipe cover following the groove
and wrap the pipes.
Pipe inlet gap
• Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-
main. (If the gaps are not closed, noise may be emitted or water and dust will
enter the unit and breakdown may result.)
* After charging the unit with refrigerant, note the added refrigerant amount on
the service label (attached to the unit).
Refer to the "1.5. Using R410A refrigerant air conditioners" for more informa-
tion.
• Be careful when installing multiple units. Connecting to an incorrect indoor unit
can lead to abnormally high pressure and have a serious effect on operation per-
formance.
2
G), wait five minutes, and make sure the
2
G), wait five minutes, and make sure the
2
G) for the RP200 or to 4.15 MPa (41.5

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Mr. slim puhz-rp250yha2

Inhaltsverzeichnis