Operating instructions level transmitter
SAFETY NOTES
The level transmitter P142 is a hydrostatic pressure sensor for measuring 
the level of liquids. If used incorrectly, application related dangers may 
arise, e.g. product overflow through incorrect installation or adjustment. 
The transmitter must be installed, connected, commissioned, operated 
and maintained by qualified and authorised personnel only, under strict 
observance of these operating instructions, relevant national standards 
legal requirements, and where appropriate, the product certification. 
Operating pressures and overpressures are to be observed, see type label 
and data sheet.
SPECIFIC CONDITIONS OF USE
1. It must be ensured that there is no damage to the membrane during 
installation, operation or maintenance. Dangers caused by aggressive 
media or mechanical stress must be excluded. If the membrane is 
damaged, the level probe must be taken out of operation and replaced 
immediately. Repairs can only be carried out by the manufacturer. With 
a damaged membrane, neither the intrinsic safety of the probe nor its 
measurement accuracy can be guaranteed.
2. The connection cable must be laid protected. Static charge and 
mechanical stress must be excluded. The manufacturer is not liable for 
damage resulting from improper use.
3. The housing of the probe must be connected to the equipotential
bonding of the system by a direct conductive connection or by connec-
ting the cable shielding.
INSTALLATION
The protective cap should remain mounted during operation because it 
protects the membrane from contaminants in the medium. The function 
of the transmitter is nearly independent of its orientation. A sideways 
movement of the cable probe can lead to measuring errors. 
Therefore, install the probe at a point free from flow and turbulence, 
or use a guide tube. The cable must end in a dry room or in a proper 
terminal housing with GORE-TEX® filter.

OPERATING CONDITIONS

Ui ≤ 30 V, Ii ≤ 150 mA, Pi ≤ 750 mW
The effective internal inductance of level transmitter and cable 
conntection is 0 µH + cable length [m] * 1 µH/m
The effective internal capacitance of level transmitter and cable 
conntection is 11,12 nF + cable length [m] * 200 pF/m
PT100 or PT1000 option only: Ui ≤ 20 V, Ii ≤ 320 mA, Pi ≤ 100 mW
The effective internal inductance of level transmitter and cable 
conntection is 0 µH + cable length [m] * 1 µH/m
The effective internal capacitance of level transmitter and cable 
conntection is 0 nF + cable length [m] * 200 pF/m
All electrostatic charges of cables or plastic components through friction 
or flowing media must be prevented by the user.
Nöding Messtechnik GmbH  •  Oldenfelder Bogen 29  •  D-22143 Hamburg, Germany  •  Tel.: +49  40  67 58 51 – 0
Fax: +49  40  67 58 51 – 49  •  Internet: www.noeding-messtechnik.de  •  E-mail: info@noeding-messtechnik.de

INSTALLATION NOTE

Vented cable, do not close off capillary! 
Protect from ingress of water!
Protect membrane from damage

INSTALLATION EXAMPLES

Cable clamp 
Junction box 
AKL1-304
                 KG1
floating/lying 
freely
screwed in from outside
e.g. flange, shut-off valve,
thread fitting
EN