Electrical Connection - Helios Rmk Montage- Und Betriebsvorschrift

Kanalrauchmelder
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
CHAPTER 4
ELECTRICAL
CONNECTION
m
DANGER
ATTENTION
Fig.6
E
smoke-
detection
-
24V DC
+
+
evaluation
unit
853
84
001 SS-110
7 17.09.19
Duct smoke detector – RMK

4.1 Electrical connection

m Danger to life due to electric shock!
Before any maintenance or installation work or before opening the terminal
compartment, the unit must be fully isolated from the power supply and secured
against unintended restart!
The electrical connections and electrical commissioning may only be carried out by quali-
fied electricians according to the information in the following wiring diagram.
The relevant national standards, safety regulations and instructions (e.g. DIN EN VDE
0100) as well as the technical connection conditions of the energy supply company must
be observed!
The connection cable is fed through the included cable gland and professionally connec-
ted. The optical smoke detector is then screwed into the ventilation duct base. The inlet
pipe with flow adapter is also used.
As a result, a functional test must be carried out using test gas (aerosol)!
– Wiring diagram
Reset
RMK
Ref.no 4982
.
max.
30V DC
1A
1 2
4
5
4
Functional position of the relay contact
Operating condition
4
- slightly soiled
5
- heavily soiled
4
- without tension
- Fault
5
- alarm
max. number of detectors see
instructions for the evaluation unit
If there are several RMKs, wire the relay
contacts so that the line is interrupted when
one RMK is removed (all contacts in series).
1 2
1 2
5
4
4
5
EN
-
+
+