RF Rx SW868/SW915/SW917/SW922-4W 24VAC/DC
Montage- und Anschlussanleitung / Funk-Empfänger
Mounting and wiring instructions / Wireless receiver
English
In these variants the status monitoring or status and battery monitor-
ing functions are always activated (factory setting of status monitoring
to 10 s).
Start-up
Requirements:
- Mount device on a standard DIN rail.
- Connect cable for supply voltage 24 VAC/DC.
- A maximum of 40 transmitters can be taught in parallelly.
- The green LED indicates operational readiness.
The orange LED indicates the state of the output:
Off - Transmitter taught in, but inactive,
On - Transmitter taught in, active,
LED 1 flashes - No transmitter taught in.

Configuration mode

The receiver's operating modes and the behaviour of the transmitter
are set here.
Start configuration mode:
- Press and hold button S1 for 10 s
→ the MD LED flashes quickly (5 Hz).
- Release button S1
→ LED1 flashes once with a 1-second pause.
Objective
Action
Current menu item
Vertical navigation
Press button S1
briefly (< 1 s).
Horizontal
Press and hold but-
ton S1 for at least
navigation 
1 s.
Save configuration
Press and hold but-
ton S1 for at least
1 s.
Cancel
Press and hold the
configuration 
S1 button for > 10 s
or button timeout
≥ 5 min.
Overview of configuration mode: see Figure p. 9
Select operation mode
These settings relate to the behaviour of the receiver. There are three
function groups for this: »Relay function«, »Transmitter function« and
»Additional function«. The relay function is used to set the behaviour
of the switching relays. The transmitter function enables a logical link
(with several taught-in switches per channel), current impulse func-
tion or wiper function. The additional options »Battery monitoring«
and/or »Status monitoring« are used to monitor the wireless switches.
Operating
mode
Standard
Standard,
inverse output
Relay energised
Relay energised,
inverse output
Standard
Blinking behaviour
Link
LED 1 flashes seve-
ral times
Latching
function
Wiper
function
Cancellation con-
firmation: LED MD
and LED 1 flash 6
times quickly.
6 / 16
Blink-Code LED 1
Relay functions
1 – 1 – 1
1 – 1 – 2
1 – 1 – 3
1 – 1 – 4
Transmitter functions
1 – 2 – 1
AND
1 – 2 – 2 – 1
OR
1 – 2 – 2 – 2
EX-OR
1 – 2 – 2 – 3
1 – 2 – 3
0,5 s
1 – 2 – 4 – 1
1 s
1 – 2 – 4 – 2
2 s
1 – 2 – 4 – 3
5 s
1 – 2 – 4 – 4
120 s
1 – 2 – 4 – 5
300 s
1 – 2 – 4 – 6
600 s
1 – 2 – 4 – 7
flexible
1 – 2 – 4 – 8 – 1...600
Function
Relay energises
when actuated
Relay de-energises
when actuated,
inverse output
signal.
Relay energises
when operating
voltage is applied.
Relay energises
when operating
voltage is applied,
inverse output
signal.
The output takes
on the last switch
status received.
The following links
can be selected:
OR, AND, EXCLU-
SIVE-OR.
Latching function /
impulse function
Wiper function,
contact drops out
automatically after
set time. In additi-
on to the predefi-
ned times, a flexi-
ble time between
1 and 600 s can be
selected.