Startup
Check settings before startup
Check of the burner head
Checks before startup.
The following points must be checked
before first use.
· Correct installation of burner as per
instructions supplied.
· Correct pre-adjustment of burner as
per data given in table of settings.
· Adjustment of burner head, the
correct nozzle must be installed. The
heat generator must be installed and
ready for operation, the operating
instructions of the heat generator
should be observed.
· All electrical connections must be
carried out correctly.
Burner
Burner power
kW
st
d
1
stage
2
stage
EK03B.24
85
120
138
196
170
240
EK03B.30
140
200
172
245
210
300
The above adjustment data correspond
to the default settings. Pre-delivery
adjustment settings appear within a
black rectangle.
· Heat generators and heating systems
are to be filled sufficiently with water,
with circulation pumps in operation.
· Temperature controllers, pressure
regulators, low water-level detectors
and any other safety or limiting
devices that might be fitted are
correctly connected and in operation.
· Exhaust conduits must be
unobstructed, draught stabilizers - if
fitted - must be functioning.
· Ensure that there is an adequate
supply of fresh air.
· The heat dissipation system must
function correctly.
Fuel-oil flow rate
Nozzle
kg/h
Gph
45°B
st
d
1
stage
2
stage
7.2
10.1
1.75
11.6
16.5
3.00
14.3
20.2
3.75
11.8
16.9
3.00
14.5
20.7
3.75
17.7
25.3
4.50
These settings allow the burner to be
run in normal operation, but always
carry out a careful check of adjustment
settings, as individual plant conditions
may require certain corrections.
Check of the burner head
Dismantle burner head:
· Loosen tube between pump and
nozzle line.
· Pull out photoelectric cell 1.
· Unplug ignition cable 2.
· Loosen the three fixing screws S.
· Pull out burner head.
Check burner head:
· Check nozzle size, referring - if
necessary - to the above table.
· Check ignition electrode setting and
turbulator, and adjust as required.
· Check space between nozzle and
turbulator, and adjust as required.
· Refit burner head.
0305 / 13 010 761A
· Fuel storage tanks must be filled.
· Fuel conduits must be correctly fitted,
checked for leaks and purged of air.
· A standard-compliant measuring
point must be available for the
metering of emissions, the exhaust
conduit upstream of this measuring
point must be free of leaks in order to
prevent outside air from causing
measurement errors.
Pump pressure
Dimen-
bar
sion Y
mm
st
d
1
stage
2
stage
11
22
5
11
22
20
11
22
30
11
22
15
11
22
18
11
22
40
The following nozzles types must be
used to ensure favorable combustion
values:
Danfoss 45° B
EN
Air-flap adjustment
setting
st
d
1
stage
2
stage
Cam IV
Cam I
0
20
20
50
30
60
20
55
30
80
35
90
25