Function
Automatic control unit SH 213
Blink-code
x x
Wait for enable by the pre-heater thermostat
x x x
Pre-aeration time/pre-ignition time
x y y y y
No flame signal at the end of safety time.
x x y y y
If an unauthorised flame is detected during the
pre-ventilation/pre-ignition time.
x x y y y — y y y y y
Manual safety shutdown (refer also to locking procedure).
Code
x
Short light signal
y
Long light signal
Pause
Required input signals
Output signals
Temperature controller Pre-heater
1
Activation of automatic unit (and of pre-heater)
2
Activation of burner motor and ignition
transformer servomotor moves to full-load
position
3
Servomotor switches back to partial load
4
Activation of fuel-oil valve
5
Flame check
20
Press R
during ...
... less than 9
seconds...
... between 9 and
13 seconds....
... More than 13
seconds...
Information / Cause of malfunction
Note
Burner motor
Fuel-oil valve Regulation
6
Shutdown of ignition transformer, burner
operation part-load
7
Burner operation, regulation between part and
full load
0
Regulator shutdown
10 Malfunction mode
0305 / 13 010 761A
The SH 213 fuel-oil control unit controls and
monitors the forced-draught burner. The
... leads to ...
microprocessor-controlled program sequence
ensures the maximum consistency of the time
periods involved, regardless of fluctuations in the
power-supply voltage or ambient temperature. The
Unlocking or
design of the automatic unit protects it from the
effects of brownouts. Whenever the supply voltage
locking of the
drops below its rated minimum level, the control unit
control unit
shuts down - even if no malfunction signal has
been emitted. The control unit switches itself back
on again once the voltage has returned to normal
Delete the statistics of
levels.
the control unit
Information system
The built-in visual information system keeps you
up-to-date regarding the causes of any safety
shutdown. The most recent cause of a malfunction
No effect on the
is logged, and the information can be reconstructed
control unit
on startup of the system - even if there has been a
power failure in the meantime. In the event of a
malfunction occurring, the LED indicator in the
"Reset" button (R) lights up and stays permanently
lit until the fault has been acknowledged (i.e. until
the error has been cleared or the control unit fault
has been dealt with).
The light pauses every ten seconds to emit a
blink-code designed to indicate the cause of the
malfunction. It is possible, using the display
program (available as an accessory), to obtain
further in-depth information on the system's
operating and malfunction procedures.
Locking and unlocking the system
The automatic unit can be locked (corresponding to
a malfunction) and unlocked (cleared) by pressing
the "Reset" button (R), provided the system is
connected to the power supply.
If the button is pressed during normal or startup
mode, the device goes into malfunction mode. If the
button is pressed with the system in malfunction
mode, the automatic unit is unblocked.
m
Ignition transformer Flame monitor
tw Pre-heater waiting time
tlk Opening time of SM, pre-ventilation and
tr
ts
tn Post-ignition time
tv2 Minimum time between fuel valve 1 and 2
Always disconnect the power supply before
installing or removing the automatic unit. DO
NOT attempt to open the automatic unit, as
there are no user-serviceable parts inside.
Servomotor SM Fault
pre-ignition
Shutting time of SM
Safety time
Unlocking